C.  Low Voltage DC can be used to turn the 

control 

ON

 and 

OFF.

  Move jumper "J1" from 

terminal 7, to terminal 5, (6 remains the 
same). 

 

Connect a +5 to 30VDC (10mA) signal to 
terminal 12 and the reference (GND) to 
terminal 11 of TB2.  The control will now turn 

ON

 when the DC signal is present at terminals 

11 and 12 of TB2.  This input is optically 
isolated. Refer to Section C of the OFF/ON 
CONTROL GUIDE. 

 

D. AC 

Voltage may be used to turn the control 

ON

 and 

OFF

.  This requires a 105-250VAC 

signal, with 2mA leakage maximum.  Set up 
the control by moving the jumper "J1" from 
terminal 7, to terminal 5, (6 remains the 
same).  Connect the 105-250VAC Signal to 
terminal 12 (L1) and the common (L2) to 
terminal 10 of TB2.  The FC-40 control will 
now turn 

ON

 whenever the AC signal is 

applied to terminals 10 and 12 of TB2. This 
input is optically isolated.  Refer to Section D 
of the OFF/ON CONTROL GUIDE. 

 

TB-2 terminals 5-7 are transformer isolated from 
the line voltage circuit. 

 

4.  MAIN CONTROL DIAL

 

 

The output power is controlled by the 

MAIN 

CONTROL DIAL

.  A special logarithmic-tapered 

power out curve (non-linear) spreads the power 
broadly across the 

MAIN CONTROL DIAL

 to help 

give maximum "Fine Control" over the output 
speed of the vibratory feeder.   

 

5. SETTING THE SOFT-START

 

 

The start-up of the control output can be adjusted 
to ramp up to the desired output level instead of 
starting abruptly. This keeps parts from falling off 
the tooling of a vibratory feeder when it turns on; it 
can reduce hammering during turn on; it can also 
simulate a paddle switch ON delay.  Adjust the 

SOFT

 Start trimpot clockwise for the gentlest start 

(about a 10-second ramp up to full output).  Turn 
the trimpot fully counter-clockwise for no soft start. 
 
 

6. LINE VOLTAGE COMPENSATION 

 

Fluctuations in the line Voltage can cause a feeder 
bowl to vary its feed rate.  The line voltage 
compensation feature adjusts the control's output to 
help compensate for fluctuations in the supply 
voltage. If it becomes necessary to disable this 
feature, remove resistor R4 from the bottom of the 
board with a pair of pliers, twist R4 to snap it off. 
 

 

  

7.  REMOTE SPEED CONTROL 

 

Remote control of the power signal level can be 
accomplished by the following methods: 

 

A.   0-5VDC Analog input signal may be applied in 

place of the Main Control Dial.   For further 
information, contact  RODIX. 

 

B. 4-20mA signal from a PLC can be used to 

remotely vary the output of the control instead of 
the Main Control Dial.  This feature is automatically 
turned on whenever a 4-20mA signal is applied to 
the control.  To return control to the Main Control 
Dial, remove the 4-20mA signal by turning it off or 
use a switch to open the circuit.  The 4-20mA input 
is transformer isolated from the power line. 

 

C.   Remote control of the output power level can be 

accomplished by using an optional 

Step Up/Down 

Remote Speed Interface P/N 123-148

.   

 

WARNING: 

 

Fuses should be replaced with Littelfuse 3AB 
"Fast Acting" type or equivalent of manufacturer's 
original value. 

 

Mounting this control on a vibrating surface will 
void the warranty. 

 

 WARRANTY

 

 

Rodix Control Products are Warranted to be free 
from defects in material and workmanship under 
normal use for a period of two years from date of 
shipment.  

For the full description of the warranty, 

terms, and software license, please contact the 
factory.

 

 
For assistance installing or operating your Rodix 
Control please call the factory.  Technical help is 

available to answer your questions and Fax any 
needed information.  To return a control for IN or 
OUT of Warranty Service, please ship it prepaid 
to: 

Rodix Inc.,  ATTN: Repair Department

 

 
If under Warranty, Rodix will repair or replace your 
control at no charge; If out of Warranty, we will 
repair it and you will be billed for the repair charges 
(Time and Material) plus the return freight.  Quotes 
for repairs are available upon request.  A brief note 
describing the symptoms is appreciated by our 
Technicians.

 

 