MODEL FC-48H-PLC
Plus
Plus
Plus
Plus
P/N 121-690
Listed, File No.
E183233
Input: 240 VAC
50/60
HZ.
Output: 0-240 VAC
Single Unit Fuse Size: 15 AMPS
80% Duty Cycle at Rated AMPS
© 2000
RODIX
INC
....
1. SELECTING 60 OR 120 PULSE
OPERATION
A. For 60 pulse output - Set switch (S1) to 60 on
"master control" P.C. card (No. 24-489).
B. For 120 pulse output - Set switch (S1) to 120 on
"master control" P.C. card.
Note: Readjust MAX pot after changing pulse
switch setting.
2. LIMITING THE MAXIMUM
OUTPUT OF CONTROL
Adjust the
MAX
Output trimpot so that the output to
the feeder reaches its desired maximum level when
the
MAIN CONTROL DIAL
is turned fully clockwise.
The
MAX
Output trimpot should be adjusted to keep
the vibratory feeder from hammering when the control
is turned up to full power.
NOTE: Output to feeder must be connected and
the control set for proper output frequency (60 or
120 pulse) setting. The Run Jumper must be
connected as shown on the wiring diagram.
A. Power input should be
OFF
or disconnected.
B. Rotate
MAIN CONTROL DIAL
on front cover to 0
or its minimum setting.
C. Open cover to allow access to printed circuit
card.
D. Using
CAUTION
, turn power
ON
(no output
should be present).
E. Rotate the
MAIN CONTROL DIAL
on front cover
slowly to its highest setting.
F. Adjust the
MAX
Output trimpot so that the output
to the feeder reaches its desired maximum level
when the
MAIN CONTROL DIAL
is turned fully
clockwise. Turning the
MAX
Output trimpot
clockwise increases the maximum output
level.
3. REMOTE OFF/ON CONTROL
Note: a Run Jumper has been installed at the
factory as shown on the enclosed wiring diagram.
Remote OFF/ON operation of the FC-40
Plus
Plus
Plus
Plus
Series
Series
Series
Series
Feeder Cube
®
control can be configured
to operate in one of the following ways.
A. A low current switch such as a paddle switch
can replace the factory-installed Run jumper
"J1." The "Run Contact" connects to
terminals 6 and 7. The contact must be able
to switch 5VDC and 2mA. The control will
then run only when the contact is closed.
Refer to Section A of the OFF/ON CONTROL
GUIDE.
B.
Feeder Bowl/Hopper Interlock allows the
Hopper control to operate only when the Bowl
is running and the paddle switch contact is
closed. The
interlock input
on terminals 11
and 12 of TB2 is controlled by the
interlock
output
of a "Parts Sensing Feeder Bowl
Control" such as an FC-90
Plus
Plus
Plus
Plus
.
Remove jumper "J1" of this control from
terminals 6 and 7. Connect the Hopper
Paddle switch to alternate terminals 5 and 6.
Connect TB2 terminals 11 and 12 of this
control to the "Parts Sensing Control". Refer
to Section B of the OFF/ON CONTROL
GUIDE. Check specific instructions for the
"Parts Sensing Control" wiring.
Note: Only use the Bowl/Hopper Interlock with
a FC-90 and FC-40 Series control. Two FC-
40 Series controls will not interlock to each
other since neither one has an
interlock
output
.
48h-plc.doc 9/28/2009
RODIX INC.
FEEDER CUBE
FC-40
Plus Series
Plus Series
Plus Series
Plus Series
OIL RESISTANT
ADJUSTMENTS AND
SET UP