Ground the Cabinet
HAZARD OF ELECTRIC SHOCK
Connection of the cabinet to building Common Bonding Network (CBN) is required.
Failure to follow these instructions will result in death or serious injury.
DANGER
Please note that each cabinet should be bonded directly to a common ground using one of the designated
grounding points (M6 threaded inserts) at the bottom of the cabinet.
• All enclosure doors have a pre-installed ground wire connected to the enclosure frame.
• To connect the enclosure to facility's ground, please use the reserved grounding holes
on the base of the front or rear door frame.
• Install an 8 AWG wire with the included M6 screw, and connect the other side of the
wire to the facility's grounding point.