Programming and Parameters
2-37
Selected Option Definitions – [Analog Outx Sel], [Digital Inx Sel], [Digital Outx Sel]
INPUTS/OUTPUTS
Digital Outputs
381
385
389
[Dig Out1 Level]
[Dig Out2 Level]
[Dig Out3 Level]
Sets the relay activation level for options
10 – 15 in [Digital Outx Sel]. Units are
assumed to match the above selection
(i.e. “At Freq” = Hz, “At Torque” = Amps).
Default:
Min/Max:
Units:
0.0
0.0
0.0
0.0/1500.0
0.1
382
386
390
[Dig Out1 OnTime]
[Dig Out2 OnTime]
[Dig Out3 OnTime]
Sets the “ON Delay” time for the digital
outputs. This is the time between the
occurrence of a condition and activation
of the relay.
Default:
Min/Max:
Units:
0.00 Secs
0.00 Secs
0.00 Secs
0.00/163.00 Secs
0.01 Secs
383
387
391
[Dig Out1 OffTime]
[Dig Out2 OffTime]
[Dig Out3 OffTime]
Sets the “OFF Delay” time for the digital
outputs. This is the time between the
disappearance of a condition and
de-activation of the relay.
Default:
Min/Max:
Units:
0.00 Secs
0.00 Secs
0.00 Secs
0.00/163.00 Secs
0.01 Secs
File
Gr
oup
No.
Parameter Name & Description
Values
Related
Option
Description
Related
At Speed
Relay changes state when drive has reached commanded speed.
Excl Link
Links digital input to a digital output if the output is set to “Input 1-6
Link.” This does not need to be selected in the Vector option.
Input 1-6 Link
When Digital Output 1 is set to one of these (i.e. Input 3 Link) in
conjunction with Digital Input 3 set to “Excl Link,” the Digital Input 3
state (on/off) is echoed in the Digital Output 1.
MOP Dec
Decrements speed reference as long as input is closed.
MOP Inc
Increments speed reference as long as input is closed.
Param Cntl
(A.O.)
Parameter controlled analog output allows PLC to control analog
outputs through data links. Set in [AnlgX Out Setpt], par. 377-378.
Param Cntl
(D.O.)
Parameter controlled digital output allows PLC to control digital
outputs through data links. Set in [Dig Out Setpt], parameter 379.
PI Reference
Reference for PI block (see
Run Level
Provides a run level input. A run level input does not require a
transition for enable or fault, but does require a transition for a stop. If
a “Stop” input is used to reset faults the “Run Level” input must be
transitioned when the 24V DC internal supply is used.
Run w Comm
Allows the Comms start bit to operate like a run with the run input on
the terminal block. Ownership rules apply.