2-36
Programming and Parameters
INPUTS/OUTPUTS
Digita
l Out
p
ut
s
379
[Dig Out Setpt]
Sets the digital output value from a communication device.
Example
Set [Data In B1] to “379.” The first three bits of this value will determine the setting
of [Digital Outx Sel] which should be set to value 30 “Param Cntl.”
380
384
388
[Digital Out1 Sel]
[Digital Out2 Sel]
[Digital Out3 Sel]
Selects the drive status that will energize
a (CRx) output relay.
(1 )
Any relay programmed as Fault or Alarm
will energize (pick up) when power is
applied to drive and deenergize (drop out)
when a fault or alarm exists. Relays
selected for other functions will energize
only when that condition exists and will
deenergize when condition is removed.
(2)
Activation level is defined in [Dig Outx
Level] below.
(3)
Refer to Option Definitions on
.
Default:
Options:
1
4
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21-26
27
28
29
30
“Fault”
“Run”
“Run”
“Fault”
(1)
“Alarm”
(1)
“Ready”
“Run”
“Forward Run”
“Reverse Run”
“Auto Restart”
“Powerup Run”
“At Speed”
“At Freq”
(2)
“At Current”
(2)
“At Torque”
“At Temp”
(2)
“At Bus Volts”
(2)
“At PI Error”
(2)
“DC Braking”
“Curr Limit”
“Reserved”
“Motor Overld”
“Power Loss”
“Input 1-6 Link”
“PI Enable”
“PI Hold”
“Reserved”
“Param Cntl”
(3)
002
001
003
004
218
012
137
157
147
053
048
184
File
Gr
oup
No.
Parameter Name & Description
Values
Related
0
0
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Output Energized
0
=Output De-energized
x =Reserved
Bit #
Net DigOut1
Net DigOut2
Net DigOut3