2-26
Programming and Parameters
UTILITY
Diagnostics
220
[Motor OL Count]
Accumulated percentage of motor
overload. Continuously operating the
motor over 100% of the motor overload
setting will increase this value to 100%
and cause a drive fault.
Default:
Min/Max:
Units:
Read Only
0.0/100.0%
0.1%
224
[Fault Frequency]
Captures and displays the output speed
of the drive at the time of the last fault.
Default:
Min/Max:
Units:
Read Only
0.0/+[Maximum Freq]
0.1 Hz
thru
225
[Fault Amps]
Captures and displays motor amps at the
time of the last fault.
Default:
Min/Max:
Units:
Read Only
0.0/[Rated Amps]
×
2
0.1 Amps
thru
226
[Fault Bus Volts]
Captures and displays the DC bus voltage
of the drive at the time of the last fault.
Default:
Min/Max:
Units:
Read Only
0.0/Max Bus Volts
0.1 VDC
thru
227
[Status 1 @ Fault]
Captures and displays [Drive Status 1] bit pattern at
the time of the last fault.
Read Only
thru
228
[Status 2 @ Fault]
Captures and displays [Drive Status 2] bit pattern at
the time of the last fault.
Read Only
thru
229
[Alarm 1 @ Fault]
Captures and displays [Drive Alarm 1] at the time of
the last fault.
Notes: Bit 15 was added for firmware version 2.001.
Bits 7, 8 and 14 were changed to “Reserved” for
firmware version 3.001.
Read Only
thru
File
Gr
oup
No.
Parameter Name & Description
Values
Related
0
1
1
0
0
0
0
1
0
1
1
1
0
0
0
0
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Read
y
Active
Command Dir
Actual Dir
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local ID 0
Local ID 1
Local ID 2
Spd Ref ID 0
Spd Ref ID 1
Spd Ref ID 2
Spd Ref ID 3
0
0
0
0
0
0
0
0
0
0
0
0
0
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
= Condition True
0
= Condition False
x = Reserved
Bit #
Read
y
Active
Running
Jog
ging
Stopping
DC Braking
A
utoT
uning
A
utoRst Ctdn
A
utoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k
x
Reser
ved
Reser
ved
Reser
ved
0
0
0
0
0
0
0
0
0
0
0
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
= Condition True/Enabled
0
= Condition False/Disabled
x = Reserved
Bit #
Prec
hr
g Actv
UnderV
olta
ge
Po
wer Loss
Str At PwrUp
Anlg in Loss
IntDBRes OH
Decel Inhibt
W
aking
Motor Therm
Phase Loss
Load Loss
Reser
ved
Reser
ved
Gate Disab
le
Heatsink T
emp
0
x
x
0
Reser
ved
x
Содержание powerflex 700h
Страница 1: ...PROGRAMMING MANUAL High Power Firmware Versions x xxx 3 001 PowerFlex 700H AC Drives ...
Страница 10: ...P 4 Overview Notes ...
Страница 56: ...2 42 Programming and Parameters Notes ...
Страница 70: ...3 14 Troubleshooting Notes ...