47
Real-time clock registers SR289 to SR297
(W2849 to W2857)
Sets the time of the built-in clock (RTC) and stores and displays the
present time. Data is stored in BCD format.
(
○
: bit = 0;
×
: bit change)
* Usable for NX70-CPU70p2 module only
In SR289, the year can be read in a 4-digit BCD.
Ex) $1998=1998, $2000=2000
SR289 to SR297 for clock functions are shown in BCD, so it is convenient to confirm in HEX.
Set the range as follows:
Year: 00 to 99, Month: 01 to 12, Day: 01 to 31, Day of Week: 01 to 07 (Sun. to Sat.)
Hour: 00 to 23, Minute: 00 to 59, Second: 00 to 59
1. Ladder setting method:
For example, current date and time are: Tuesday, March 21, 1996, 18:35:07
2. When changing the year, month, date, or day, new data is input in SR295, SR294, then the F12.14 bit is turned
On. The F12.10 bit is kept Off.
3. When changing the hour, minute, and second, new data is input in SR297, SR296, then the F12.14 bit is turned
on. If the new data is not set correctly, the F12.10 bit turns on.
4. The display date and set value are expressed in BCD so it is convenient to input as hex ($).
5. The year, month, and day are automatically changed.
Cl
ass
if
ica
tio
n
Ad
d
re
s
s
Bit address
Adjustment/
indication
Details
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Current
time
SR289
Year
(4-digit BCD)
SR290
Date: day
○
○
×
×
×
×
×
×
○
○
○
○
○
×
×
×
SR291
Year: month
○
×
×
×
×
×
×
×
○
○
○
×
×
×
×
×
SR292
Second: 00
○
○
×
×
×
×
×
×
○
○
○
○
○
○
○
○
SR293
Hour: minute
○
○
×
×
×
×
×
×
○
○
○
○
○
○
○
○
Time
setting
SR294
Date: day
○
○
×
×
×
×
×
×
○
○
○
○
○
×
×
×
SR295
Year: month
○
×
×
×
×
×
×
×
○
○
○
×
×
×
×
×
SR296
Second: 00
○
○
×
×
×
×
×
×
○
○
○
○
○
○
○
○
SR297
Hour: minute
○
○
×
×
×
×
×
×
○
○
○
○
○
○
○
○
NOTE
Designate year, month, day
Designate hour, minute, second
Date indicators are
Sun (01), Mon (02), Tue (03),
Wed (04), Thu (05), Fri (06),
and Sat (07)
Содержание Samsung NX-CPU700p
Страница 1: ...NX700 Series Controller NX CPU700p User Manual ...
Страница 78: ...78 Power check flow chart ...
Страница 79: ...79 Run check flow chart ...
Страница 80: ...80 Error check flow chart ...
Страница 82: ...82 External environment check flow chart ...
Страница 86: ...86 ...
Страница 98: ...98 ...
Страница 102: ...102 Decimal Bin Hex BCD Gray Code Cross reference Table ...
Страница 104: ...104 ...
Страница 121: ......