2-6
Installing the Adapter
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Configuring/Verifying Key Drive Parameters
The PowerFlex 755 drive can be separately configured for the control
and Reference functions in various combinations. For example, you
could set the drive to have its control come from a peripheral or
terminal block with the Reference coming from the network. Or you
could set the drive to have its control come from the network with the
Reference coming from another peripheral or terminal block. Or you
could set the drive to have both its control and Reference come from the
network.
The following steps in this section assume that the drive will receive the
Logic Command and Reference from the network.
1. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed
Reference to “Port 13 Reference” (the drive port dedicated to the
embedded EtherNet/IP adapter).
2. Verify that drive Parameter 930 - [Speed Ref Source] is reporting
that the source of the Reference to the drive is “Port 13 Reference.”
This ensures that any Reference commanded from the network can
be monitored by using drive Parameter 002 - [Commanded
SpdRef]. If a problem occurs, this verification step provides the
diagnostic capability to determine whether the drive/adapter or the
network is the cause.
3. If hard-wired discrete digital inputs are not used to control the
drive, verify that all unused digital input parameters are set to “Not
Used.”
Commissioning the Adapter
To commission the embedded EtherNet/IP adapter, you must set a
unique IP address. See the
for details about IP addresses.
When using the adapter switches, refer to
. When not using the adapter switches, use either a
BOOTP server or adapter parameters to set the IP address after
connecting the adapter to the network and applying power to the drive.
By default, the adapter is configured so that you must set the IP address
using a BOOTP server. For details, see
. To
set the IP address using adapter parameters, refer to
Address, Subnet Mask, and Gateway Address on page 3-5
.
Important: New settings for some adapter parameters (for example,
Parameters 38 - [IP Addr Cfg 1] through 41 - [IP Addr
Cfg 4]) are recognized only when power is applied to the
adapter or it is reset. After you change parameter settings,
cycle power or reset the adapter.
Содержание PowerFlex 755 Drive
Страница 1: ...USER MANUAL Firmware Version 1 xxx PowerFlex 755 Drive Embedded EtherNet IP Adapter...
Страница 152: ...7 6 Troubleshooting PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 166: ...A 2 Specifications PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 224: ...G 8 Glossary PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 229: ...Index 5 PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 230: ...Index 6 PowerFlex 755 Drive Embedded EtherNet IP Adapter User Manual Publication 750COM UM001A EN P Notes...
Страница 231: ......