36
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
PowerFlex 753 Drive (P_PF753)
condition is required. Once the alarm is acknowledged, the alarm border and
label background remain the color that corresponds to the severity of the alarm.
See Rockwell Automation Library of Process Objects: Common Alarm Block
(P_Alarm) Reference Manual, publication
SYSLIB-RM002
, for more
information.
Maintenance Bypass Indicator
This symbol appears to the right of the label to indicate that a maintenance
bypass has been activated.
For the PowerFlex 753 Drive Instruction, the Maintenance Bypass Indicator
appears when the bypassable interlocks and permissives have been bypassed.
Symbol
Border and Label Background
Description
No change in color
Alarm Inhibit: an alarm is suppressed by the Program,
disabled by Maintenance, or shelved by the Operator.
White
Return to normal (no alarm condition), but a previous
alarm has not been acknowledged.
Blue
Low severity alarm.
Yellow
Medium severity alarm.
Red
High severity alarm.
Magenta
Urgent severity alarm.
No symbol
No change in color
No alarm or alarm inhibit condition, and all alarms
are acknowledged.
TIP
When the Maintenance Bypass Indicator appears, you can find what condition
was bypassed by following the indicators. Click the graphic symbol to open the
faceplate. The Maintenance Bypass Indicator appears next to the appropriate
tab at the top of the faceplate to guide you in finding the bypass. Once you
navigate to the tab, the bypassed item is flagged with this indicator.