Programming and Parameters
3-79
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
558
Trend State
Value indicates the state of the Data Trend function.
•
Value 0 - Wait Enable indicates the trend function is ready and waiting to begin data
collection. Setting bit 0 “Enbl Collect” of
[Trend Control] will cause data
collection to begin. In this state,
[TrendBuffPointer] and the Trend Output
Parameters are active.
•
Value 1 - First Scan indicates the Trend function is executing the first pass through the
trend sample buffer. This takes 512 ms. (0.5 ms x 1024 samples). When it enters this
state, the Trend function clears bit 1 “Triggered” and 2 “Complete” bits of
[Trend
Status]. While in this state, the Trend function refreshes the data. Also while in this state,
the function forces the Trend Output parameters to zero. When done, it enters the
Pre-trigger state.
•
Value 2 - Pre-trigger indicates the Trend function is sampling the trend inputs and storing
them in memory, at a rate determined by
[Trend Rate]. Sampling continues until
either the trend trigger event occurs or bit 0 “Enbl Collect” of
[Trend Control] is
cleared. While in this state, the Trend function forces the Trend Output parameters to
zero. If the trigger event occurs, the function sets bit 1 “Triggered” of
[Trend
Status] and enters the Post-trigger state. If bit 0 “Enbl Collect” of Parameter 556 [Trend
Control] is cleared, the function sets bit 2 “Complete” of Par 557 [Trend Status] and
returns to the Wait Enable state.
•
Value 3 - Post-trigger indicates the Trend function is continuing to sample and save the
trend inputs until the buffer is full. While in this state, the function forces the Trend Output
parameters to zero value. When the buffer is full, the function sets bit 2 “Complete” of
[Trend Status] and enters the Wait Disable state.
•
Value 4 - Wait Disable indicates the Trend function is complete and waiting for bit 0 “Enbl
Collect” of
[Trend Control] to be cleared. When this is done, the trend function
returns to the Wait Enable state. While in the Wait Disable state,
[TrendBuffPointer] and the Trend Output Parameters are active.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
“Wait Enable”
“Wait Enable”
“First Scan”
“Pre-trigger”
“Post-trigger”
“Wait Disable”
559
Trend Rate
Sets the sample time for both trend input and output updates.
Units:
Default:
Min/Max:
mSec
0.5000
0.5000/1000.0000
✓
RW Real
560
Trend TrigA DInt
Provides the integer input for the A trigger function. This integer is converted to a real
number and summed with
[Trend TrigA Real]. The result is compared with the
Trigger B sum. If the A sum exceeds the B sum, then a trend trigger will occur.
Default:
Min/Max:
0
-/+2147483648
✓
RW 32-bit
Integer
561
Trend TrigA Real
Provides the real input for the A trigger function. This real number is summed with
[Trend TrigA Int]. The result is compared with the Trigger B sum. If the A sum exceeds the B
sum, then a trend trigger will occur.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
562
Trend TrigB DInt
Provides the integer input for the B trigger function. This integer is converted to a real
number and summed with
[Trend TrigB Real]. The result is compared with the
Trigger A sum. If the A sum exceeds the B sum, then a trend trigger will occur.
Default:
Min/Max:
0
-/+2147483648
✓
RW 32-bit
Integer
563
Trend TrigB Real
Provides the real input for the B trigger function. This real number is summed with
[Trend TrigB Int]. The result is compared with the Trigger A sum. If the A sum exceeds the B
sum, then a trend trigger will occur.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
564
Trend Trig Data
This is the logic input for the Trend Trigger Function. A trigger will occur on the rise of the
specified bit in this word. The bit will be specified by
[Trend Trig Bit].
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
✓
RW 32-bit
Boolean
565
Trend Trig Bit
Specifies the bit in
[Trend Trig Data] that will cause a Trend Trigger to occur.
Positive numbers specify rising edges and negative numbers specify falling edges.
Default:
Min/Max:
0
-32/31
✓
RW 16-bit
Integer
566
Trend PreSamples
Specifies the number pre-trigger samples in the trend buffer. Pre-trigger samples are the
samples that occur before the trigger and remain in the buffer. The remainder of the trend
buffer will contain post-trigger samples.
Default:
Min/Max:
511
0/1022 j
✓
RW 16-bit
Integer
567
Trend Mark DInt
Marks the start of data for trend buffers that are using integer data. The Trend Marker can
be used to provide a scope trigger signal for the Auto Output function.
Default:
Min/Max:
0
-/+2147483648
✓
RW 32-bit
Integer
568
Trend Mark Real
Marks the start of data for trend buffers that are using real data. The Trend Marker can be
used to provide a scope trigger signal for the Auto Output function.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
569
TrendBuffPointer
Selects the trend buffer element to be displayed in the Trend Output Parameters when the
trend function is inactive (not collecting data samples). A zero value points to the element
that corresponds to the trigger event. Negative values point to pre-trigger data. Positive
values point to post-trigger data. When the Auto Output function is running, this parameter
will automatically sequence through it's full range, at a rate set by
[Trend Rate].
Default:
Min/Max:
0
-/+1023
✓
RW 16-bit
Integer
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
V
a
l 2
Pre-Trigger
V
a
l 0
W
a
it En
ab
le
V
a
l 1
Fir
s
t
S
c
a
n
V
a
l
3
Po
s
t-Trigger
V
a
l 4
W
a
it Di
sab
le
En
b
l Collect
En
b
l Collect
Done
Trigger Event
B
u
ffer F
u
ll
En
b
l Collect
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......