MSR300 Safety System Manual
Rockwell Automation
MSR300 Manual.doc
Pg 21 of 85
4 MSR300
Modules:
Details
4.1
MSR310 Base Module
Functions:
System control, safety and auxiliary output contacts, supervision of
bus-connected input and output modules.
Auxiliary outputs:
3 solid-state switch outputs for signaling the states of output
groups.
Serial data interface: two RS232 ports (bi-directional and uni-directional).
Selectable start mode: Monitored (manual) or automatic.
The MSR310 has independent feedback loops for each output group.
There are no safety inputs or outputs on this module.
The MSR310 Base Module has three microprocessors: for redundancy and supervision of
I/O modules. Comprehensive diagnostic information is available via two-color LED
indicators, auxiliary solid-state switch outputs and the serial data interface.
4.1.1 Terminals
Name
Function
A1
24 VDC
A2
Supply 0 V ; ground for solid-state switch outputs
GND, TxD1, RxD1 Bi-directional RS232
GND, TxD2
Uni-directional RS232
S11 – S51
Pulse train outputs (bus) to input devices
MSR310 Internal Block Schematic Diagram
MSR310