![Rockwell Automation MD60 Скачать руководство пользователя страница 52](http://html.mh-extra.com/html/rockwell-automation/md60/md60_user-manual_1475501052.webp)
9-2
MD60 AC Drive User Manual
9.1
Basic Program Group Parameters
The Basic Program Group contains the most commonly used
parameters to simplify the start-up process.
Set to the motor nameplate rated volts.
Set to the motor nameplate rated frequency.
Set to the maximum allowable motor current. The drive will fault on
an F7 Motor Overload if the value of this parameter is exceeded by
150% for 60 seconds or 200% for 3 seconds.
Sets the lowest frequency the drive will output continuously.
Sets the highest frequency the drive will output.
P031 Motor NP Volts
Range:
20 VAC to Drive Rated Volts
Default:
Based on Drive Rating
See also:
A084
P032 Motor NP Hertz
Range:
10 to 240 Hz
Default:
60 Hz
See also:
A084
P033 Motor OL Current
Range:
0.0 to (Drive Rated Amps x 2)
Default:
Based on Drive Rating
See also:
A089, A090, A098
P034 Minimum Frequency
Range:
0.0 to 240.0 Hz
Default:
0.0 Hz
See also:
d001, d002, d013, P035, A110, A112, A115
P035
Maximum Frequency
Range:
0 to 240 Hz
Default:
60 Hz
See also:
d001, d002, d013, P034, A078, A111, A113, A115
Содержание MD60
Страница 1: ...Instruction Manual MD60 AC Drive User Manual Version 3 0 D2 3499 3 ...
Страница 6: ...IV MD60 AC Drive User Manual ...
Страница 8: ...VI MD60 AC Drive User Manual ...
Страница 10: ...VIII MD60 AC Drive User Manual ...
Страница 12: ...1 2 MD60 AC Drive User Manual ...
Страница 42: ...6 10 MD60 AC Drive User Manual ...
Страница 92: ...10 10 MD60 AC Drive User Manual ...
Страница 96: ...A 4 MD60 AC Drive User Manual ...
Страница 100: ...B 4 MD60 AC Drive User Manual ...
Страница 104: ...C 4 MD60 AC Drive User Manual ...
Страница 108: ...D 4 MD60 AC Drive User Manual ...
Страница 134: ......
Страница 135: ......
Страница 136: ...Publication D2 3499 3 September 2003 2003 Rockwell International Corporation All rights reserved ...