Working Voltage and Isolation Voltage Ratings 

   

General

Attribute

Value

Terminal screw 
torque

0.56...0.79 Nm (5...7 lb-in) (1794-TB3TK, -TB3G, -TB3GK, -TB2, -TB32, -TB3, 
-TB3K, -TB3T)

 

0.3...0.6 Nm (2.6...5.3 lb-in) (1794-TBKD)

 

1.4 Nm (12 lb-in) (1794-TBN, -TBNF, -TBNFK, -TBNK)

Supply voltage 
range (max)

FLEXBUS: 5V DC, 640 mA

 

I/O Terminals: 2A max

 

V/COM Terminals: 125V DC/AC, 50/60Hz, 10A (1794-TB3SK, -TB3TK,-TB2, -TB3, 
-TB3K, -TB3S, -TB3TK, -TB3TS)

 

V/COM Terminals: 31.2V DC/AC, 50/60Hz, 10A (1794-TB3GSK, -TB3G, -TB3GS, 
-TB3GK, -TB32, -TB32S

 

V/COM Terminals: 250V DC/AC, 50/60Hz, 10A (1794-TBN, -TBNF, -TBNFK, 
-TBNK)

1794-TBKD only

 

FLEXBUS: 5V DC, 640 mA

 

Terminal Block: 120V AC, 50/60Hz, 10A

 

Disconnecting Switch: 3A, 20m

Ω

ATTENTION

 

A disconnecting switch does not shut off the current. Make or break a circuit 
only under no-load conditions.

Isolation voltage

Capable of 250V (continuous) maximum, Basic Insulation Type, Field Wiring 
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TBN, -TBNF, 
-TBNFK, -TBNK)

 

Capable of 125V (continuous) maximum, Basic Insulation Type, Field Wiring 
Terminals to FLEXBUS, or the lesser of the installed module (1794-TB3SK, 
-TB3TK, -TB3TK, -TB3TSK, -TB2, -TB3, -TB3K, -TB3S, -TB3TS)

 

Capable of 50V (continuous) maximum, Basic Insulation Type, Field Wiring 
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TB3G, 
-TB3GS, -TB3GK,  -TB3GSK, -TB32, -TB32S)

2500V DC/sec, Field Wiring Terminals to FLEXBUS.

 

220V DC/sec, Field Wiring Terminals to Functional Ground. (1794-TBKD)

Voltage rating 

See Working Voltage and Isolation Voltage Ratings for nominal values 

Enclosure type 
rating

None (open-style)

Terminal Base 1794-

24V 

120V 

230V 

Isolation Voltage

TBN, TBNK, TBNF, TBNFK

AC/DC

AC/DC

AC/DC

Dependent upon installed 
module - refer to individual 
installation instructions for 
your specific module.

TB2, TB3, TB3K, TB3S, TB3SK

AC/DC

AC/DC

TB3T, TB3TS, TB3TK, TB3TSK

AC/DC

AC/DC

TB3G, TB3GK, TB3GS, TB3GSK

AC/DC

TB32, TB32S

AC/DC

TBKD

DC

AC

General

Attribute

Value

Wire size

0.34... 3.3 mm² (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F 
) or greater, 1.2 mm (3/64 in.) insulation max. Strip Length: 5-6 mm (0.20...0.24 in.) 
(1794-TB3SK, -TB3GSK, -TB3TSK, -TB3GK, -TB3GS, -TB32S, -TB3, -TB3K, -TB3S, 
-TB3TS, -TBN, -TBNF, -TBNFK, -TBNK)

0.34…2.1 mm² (22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F 
) or greater, 1.2 mm (3/64 in.) insulation max (1794-TBKD)

0.21... 1.3 mm² (24…16 AWG) stranded copper wire rated at 75 °C (167 °F ) or 
greater, 1.2 mm (3/64 in.) insulation max  (1794-TB3TK, -TB3G, -TB2, -TB32)

Wiring 

category

(1)

Established by installed module

North American 
temp code

T4A (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, 
-TB3S,-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S) 

 

 

T6  (1794-TB2)

IEC temp code

T4  (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S, 
-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK) 

T6 (1794-TB2)

Dimensions, 
approx. 

94 x 94 x 69 mm (HxWxD) (3.7 x 3.7 x 2.7 in.)

 

(with module installed in terminal base)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and 
Grounding Guidelines, publication 

1770-4.1.

Environmental

Attribute

Value

Operating 
temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

 

-20…70 °C (-4…158 °F)  (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, 
-TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3SK, -TB3TS, -TB3TSK, 
TB32, -TB32S, -TBN, -TBNK)

0…55 °C (32…131 °F)  (1794-TBKD)

 

-20…55 °C (-4…131 °F) (1794-TBNF, -TBNFK, -TB2)

Non-operating 
temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

 

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

 

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal 
Shock):

 

-40…85 °C (-40…185 °F)

 

-20…85 °C (-4…185 °F)  (1794-TBKD)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

 

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

 

5 g @ 10…500 Hz

Operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

30 g  (Except for 1794-TBKD)

Non-operating 
shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

50 g (Except for 1794-TBKD)

Certifications (when product is marked)

(1)

Attribute Value

UL

(1794-TB2)
UL Listed Industrial Control Equipment. See UL File E65584.

c-UL-us

(1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3TS,  
-TB3SK, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S) 
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File 
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. 
and Canada. See UL File E194810.

(1794 -TBKD, -TBNF, -TBNFK )
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File 
E65584. 

CSA

(1794-TB2, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, -TB3TK, -TB3SK, -TB3TSK, -TBN, 
-TBNK, -TB3G, -TB3GK, -TB3GS, -TB3GSK) 

 

CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D 
Hazardous Locations. See CSA File LR69960C.

(1794-TBNF, -TBNFK)

 

CSA Certified Process Control Equipment. See CSA File LR54689C.

CE

European Union 2004/108/EC EMC Directive, compliant with:

 

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity

 

EN 61000-6-4; Industrial Emissions

 

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:

 

EN 61131-2; Programmable Controllers (Clause 11)

General

Отзывы: