2

    FLEX I/O Terminal Base Units

Publication 1794-IN092E-EN-P - November 2009

North American Hazardous Location Approval

The following terminal bases are Hazardous Location approved: 1794-TBN, 
-TBNK, -TB2, -TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS, 
-TB3GSK, -TB3T, -TB3TK, -TB3TS, -TB3TSK, -TB32S, -TB32. 

European Hazardous Location Approval

The following adapters are European Zone 2 approved: 1794-TBN, -TBNK, -TB2, 
-TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS, -TB3GSK, -TB3T, 
-TB3TK, -TB3TS, -TB3TSK.

 

FLEX I/O Cage-clamp Terminal Base Units  

FLEX I/O Spring-clamp Terminal Base Units 

FLEX I/O Terminal Base Units 

FLEX I/O Fused Terminal Base Units 

FLEX I/O Knifeswitch Terminal Base Unit 

The following information applies when operating 
this equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en 
environnements dangereux :

Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for 
use in Class I Division 2 Groups A, B, C, D, Hazardous 
Locations and nonhazardous locations only. Each product is 
supplied with markings on the rating nameplate indicating 
the hazardous location temperature code. When combining 
products within a system, the most adverse temperature 
code (lowest “T” number) may be used to help determine the 
overall temperature code of the system. Combinations of 
equipment in your system are subject to investigation by the 
local Authority Having Jurisdiction at the time of 
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent 
qu’à une utilisation en environnements de Classe I Division 2 
Groupes A, B, C, D dangereux et non dangereux. Chaque produit 
est livré avec des marquages sur sa plaque d’identification qui 
indiquent le code de température pour les environnements 
dangereux. Lorsque plusieurs produits sont combinés dans un 
système, le code de température le plus défavorable (code de 
température le plus faible) peut être utilisé pour déterminer le 
code de température global du système. Les combinaisons 
d’équipements dans le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de l’installation.

WARNING

EXPLOSION HAZARD

• Do not disconnect equipment 

unless power has been removed 
or the area is known to be 
nonhazardous. 

• Do not disconnect connections to 

this equipment unless power has 
been removed or the area is 
known to be nonhazardous. 
Secure any external connections 
that mate to this equipment by 
using screws, sliding latches, 
threaded connectors, or other 
means provided with this product.

• Substitution of components may 

impair suitability for Class I, 
Division 2.

• If this product contains batteries, 

they must only be changed in an 
area known to be nonhazardous.

AVERTISSEMENT

RISQUE D’EXPLOSION

• Couper le courant ou s’assurer que 

l’environnement est classé non 
dangereux avant de débrancher 
l'équipement.

• Couper le courant ou s'assurer que 

l’environnement est classé non 
dangereux avant de débrancher les 
connecteurs. Fixer tous les 
connecteurs externes reliés à cet 
équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou 
autres moyens fournis avec ce 
produit.

• La substitution de composants peut 

rendre cet équipement inadapté à 
une utilisation en environnement de 
Classe I, Division 2.

• S’assurer que l’environnement est 

classé non dangereux avant de 
changer les piles.

European Zone 2 Certification (The following applies when the product bears the Ex 
or EEx Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by European 
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety 
Requirements relating to the design and construction of Category 3 equipment intended for use 
in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance 
with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional Zone 2 certification requirements.

This equipment is not resistant to sunlight or other sources of UV 

radiation.

This equipment must be installed in an enclosure providing at least IP54 

protection when applied in Zone 2 environments.

This equipment shall be used within its specified ratings defined by 

Allen-Bradley.

Provision shall be made to prevent the rated voltage from being 

exceeded by transient disturbances of more than 40% when applied in 
Zone 2 environments.

Secure any external connections that mate to this equipment by using 

screws, sliding latches, threaded connectors, or other means provided 
with this product.

Do not disconnect equipment unless power has been removed or the 

area is known to be nonhazardous.

Cat. No. 1794-TB2, -TB3, -TB3K, -TB32, -TB3G, -TB3GK, -TB3T, -TB3TK

1794-TB2

1794-TB3, -TB3K, -TB32, 

1

2

3

4

5

6

7

8

9

10

11

-TB3G, -TB3GK, -TB3T, -TB3TK

Description

1

Female flexbus connector

2

Terminal base unit

3

Male flexbus connector

4

Keyswitch - set to the position required for the installed module

5

Mounting holes for panel mounting

6, 7, 
8

Input/output terminal strips for connecting inputs/output wiring, commons, power 
connections, customer power supplies, chassis grounds

9

Locking tab

10

Module locking latch

11

Cover plug for male flexbus connector

12

Cold-junction compensation terminals (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK only)

13

Chassis ground terminations (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK, -TB3G, -TB3GS, 
-TB3GSK only)

14

Fuses - eight 5x20 mm (1794-TBNF, -TBNFK only)

15

Terminal strip cover (1794-TBN, -TBNK -TBNF, -TBNFK only)

16

Knife switches (1794-TBKD only)

Cat. No. 1794-TB3S, -TB3SK, -TB32S, -TB3GS, -TB3GSK, -TB3TS, -TB3TSK

1

2

3

4

5

6

7

8

9

10

11

12

13

12

Cat. No. 1794-TBN, -TBNK

1

2

3

4

5

6

8

15

10

11

9

Cat. No. 1794-TBNF, -TBNFK

6

1

14

15

11

14

2

3

4

10

9

5

6

Cat. No. 1794-TBKD

1

2

3

4

5

6, 7

6, 7

9

10

11

16

Cat. No 1794-TBKD