![Rockwell Automation ControlLogix 1756-PA72 Series C Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/rockwell-automation/controllogix-1756-pa72-series-c/controllogix-1756-pa72-series-c_installation-instructions-manual_1475769021.webp)
ControlLogix Power Supplies
21
Publication 1756-IN613A-EN-P - December 2008
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
1890 MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
1890 MHz
1V/m with 1 kHz sine-wave 80% from
2000…2700 MHz
Conducted RF
immunity
IEC 6100-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on power ports
Surge transient
immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
Oscillatory surge
withstand
IEEE C37.90.1
N/A
3 kV
Enclosure type rating
None (open style)
Voltage variation
IEC 61000-4-11
IEC 61000-4-29
60% dips for 100 ms on DC supply ports
100% dips for 50 ms on DC supply ports
±20% fluctuations for 15 min on DC supply ports
5 s interruptions on DC supply ports
10 ms interruption on DC supply ports
1756-PB72 Series C, 1756-PB75 Series B - Certifications
(1)
Certifications
(2)
1756-PB72 Series C
1756-PB75 Series B
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada, See File
E65584
c-UL-us
UL Listed for Class 1, Division 2 Group A,B,C,D Hazardous Locations, certified for
U.S. and Canada. See UL File E194810
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C
CSA
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D
Hazardous Locations. See CSA File LR69960C
FM
FM Approved Equipment for use in Class 1 Division 2 Group A, B, C, D Hazardous
Locations
1756-PB72 Series C, 1756-PB75 Series B, 1756-PC75 Series B, 1756-PH75 Series B -
Environmental Specifications
Attribute
1756-PB72
Series C
1756-PB75
Series B
1756-PC75
Series B
1756-PH75
Series B