17

Publication

  1738-IN015C-EN-E - February 2010

Radiated RF Immunity

IEC 61000-4-3:

 

10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz

 

10V/m with 200 Hz 50% Pulse 100%AM at 900 Mhz

 

10V/m with 200 Hz 50% Pulse 100%AM at 1890 Mhz

EFT/B Immunity

IEC 61000-4-4:

 

±4 kV at 5 kHz on power ports

 

±2 kV at 5 kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

 

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

 

±2 kV line-earth(CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:

 

10Vrms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Emissions

CISPR 11:

 

Group 1, Class A

Enclosure Type Rating

Meets IP65/66/67 (when marked)

Certifications

Certification

Value

Certifications:

(1)

 

(when product 

 

is marked)

CE

European Union 2004/108/EC EMC Directive, 

 

compliant with:

 

EN 61000-6-4; Industrial Emissions

 

EN 50082-2; Industrial Immunity

 

EN 61326; Meas./Control/Lab., Industrial Requirements

 

EN 61000-6-2; Industrial Immunity

 

C-Tick

Australian Radiocommunications Act, compliant 

 

with: AS/NZS CISPR 11; Industrial Emissions

(1)

See the Product Certification link at www.ab.com for Declarations of Conformity, 

 

Certificates, and other certification details.

Environmental Specifications

Содержание ArmorPoint 1738-APB

Страница 1: ...PROFIBUS Adapter Series A Catalog Number 1738 APB Inside For See Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 4 About the ArmorPoint PROFIBUS Adapter 4...

Страница 2: ...well Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of informa...

Страница 3: ...d not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication Subsequent sections of this publica...

Страница 4: ...l require an additional appropriate housing PROFIBUS connectors are sealed M12 micro style ATTENTION This equipment is sensitive to electrostatic discharge which can cause internal damage and affect n...

Страница 5: ...cation Install the Module To install the module Mount the adapter and I O bases Wire the adapter 1738 APB Profibus Out Profibus In X10 X1 Adapter Status Profibus Status PointBus Status System Power Ad...

Страница 6: ...the necessary holes for 8 M4 machine or self tapping screws 3 Mount the adapter using 8 M4 screws 4 Ground the system using the ground lug connection in the I O bases Note that the ground lug connecti...

Страница 7: ...se a small blade screwdriver to rotate the switches Line up the small notch on the switch with the number setting you wish to use The two switches are most significant digit MSD and least significant...

Страница 8: ...FIBUS Out Female 5 pin Micro M12 Reverse Keyway The recommended standard cordset for the PROFIBUS auxiliary connector is 889N F5AFC x where x equals 6 12 or 20 feet ATTENTION Make sure all connectors...

Страница 9: ...ustration and the individual indicator troubleshooting tables Troubleshoot with the Indicators 1738 APB Profibus Out Profibus In X10 X1 Adapter Status Profibus Status PointBus Status System Power Adap...

Страница 10: ...Hardware check is in progress Initialization is in progress Turn the adapter on or wait until the hardware check or initialization has finished Green Operating Normally The adapter is operating norma...

Страница 11: ...eived Adapter has received a CLEAR command from the master None Red Initialization Error or No Module Error in PROFIBUS initialization No modules are installed in the backplane Perform initialization...

Страница 12: ...check in progress Initialization in progress Turn the adapter on or wait until the hardware check or initialization has finished Green Operating Normally The adapter is operating normally None Flashi...

Страница 13: ...ter Power indicator System Power Indicator State Status Description Recommended Action Off System Power Not Applied System power is not applied Apply power Green System Power Applied System power 5V i...

Страница 14: ...current to an additional 1 3 A use a 1738 EP24DC Backplane Extension Power Supply Use multiple 1738 EP24DC modules to reach the maximum of 63 modules Cat No PointBus Current Requirements 1738 IB2M12...

Страница 15: ...ons Inches 4 41 H x 2 83 W x 2 56 D LED Indicators 1 green red Adapter status 1 green red PROFIBUS status 1 green red PointBus status 1 green System Power PointBus 5V power 1 green Adapter Power 24V f...

Страница 16: ...rature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 60 C 4 140 F Storage Temperature IEC 60068 2 1 Test Ab Un package...

Страница 17: ...00 4 6 10Vrms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Emissions CISPR 11 Group 1 Class A Enclosure Type Rating Meets IP65 66 67 when marked Certifications Certification Value Certifications 1 w...

Страница 18: ...18 Publication 1738 IN015C EN E February 2010 Notes...

Страница 19: ...19 Publication 1738 IN015C EN E February 2010 Notes...

Страница 20: ...in the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your module up an...

Отзывы: