108
Rockwell Automation Publication 750-PM101B-EN-P - April 2022
Chapter 4 Troubleshooting
193 IdCompMtrnIq
This signal displays the corresponding Iq Ref values
for IdComp during motoring operation.
REAL
PU
194 IdCompMtrnPu
This signal displays the required IdComp values
during motoring.
REAL
PU
195 IdCompRegnIq
This signal displays the corresponding Iq Ref values
for IdComp during regen operation.
REAL
PU
196 IdCompRegnPu
This signal displays the required IdComp values
during regen operation.
REAL
PU
197 FlxIdSyncRef
This signal is the d-axis current reference, which is
the output of the flux regulator.
REAL
PkA
198 NegIdsLim
If this signal is non-zero, then the flux regulator is at
negative Id current limit.
DINT
t/f
199 PosIdsLim
If this signal is non-zero, then the flux regulator is at
positive Id current limit.
DINT
t/f
200 VqsFdbkFltrd
This signal is the filtered q-axis voltage feedback.
REAL
PkV
210 FLARPM
This signal is the Slip RPM at full load amps, which is
calculated based on the filtered slip gain.
REAL
RPM
211 OmegSlipFilt
This signal is the filtered slip in rad/sec.
REAL
R/S
212 RsGain
This signal is the Rs gain, which is calculated based
on the filtered slip gain.
REAL
PU
213 SlipGnFltrd
This signal is the filtered slip gain.
REAL
R/S/A
214 SlipGnLatchd
This signal is the latched slip gain in the slip
regulator.
REAL
R/S/A
215 SlipGnLmtd
This signal is the limited slip gain, which is the slip
regulator output.
REAL
R/S/A
216 SlipLoTrqLim
If this signal is non-zero, then the slip regulator is
not active because the q-axis current reference is
below the set value.
DINT
t/f
217 SlipGnMaxLim
If this signal is non-zero, then the slip regulator is at
maximum slip gain limit.
DINT
t/f
218 SlipGnMinLim
If this signal is non-zero, then the slip regulator is at
minimum slip gain limit.
DINT
t/f
219 SlipIntegOut
This signal is the integration term of the slip
regulator output.
REAL
R/S/A
220 SlipPropOut
This signal is the proportional term of the slip
regulator output.
REAL
R/S/A
221 VdsFdbkFltrd
This signal is the filtered d-axis voltage feedback.
REAL
PkV
230 IdSyncRef
Flux current command.
REAL
PkA
231 IqSyncRef
Torque command.
REAL
PkA
232 VdSyncFF_Ref
This signal is the feed forward d-axis voltage
reference.
REAL
PkV
233 VqSyncFF_Ref
This signal is the feed forward q-axis voltage
reference.
REAL
PkV
240 LambdaDsSync
This signal is the d-axis stator flux.
REAL
VSec
241 LambdaDsFilt
This signal is the filtered d-axis stator flux.
REAL
VSec
242 LambdaQsSync
This signal is the q-axis stator flux.
REAL
VSec
243 LambdaQsFilt
This signal is the filtered q-axis stator flux.
REAL
VSec
250 TrqEst
This signal is the estimated torque in N•m.
REAL
Nm
251 TrqEstFltrd
This signal is the filtered estimated torque in N•m.
REAL
Nm
255 ActvCurLim
This is the active current limit value.
REAL
PkA
260 FluxCurMax
This is the maximum flux current value.
REAL
PkA
261 FluxCurMin
This is the minimum flux current value.
REAL
PkA
262 LambdaDsRtd
This signal is the rated d-axis stator flux.
REAL
VSec
263 MtrRtdTrq
This is the motor rated torque value in N•m that is
calculated from motor name plate data.
REAL
Nm
264 SlipGnRtd
This is the rated slip gain value.
REAL
R/S/A
Port 10 Testpoint Codes (Continued)
No. Name
Description
Data Type
Units
Содержание Allen-Bradley PowerFlex 755T Series
Страница 6: ...6 Rockwell Automation Publication 750 PM101B EN P April 2022 Preface Notes ...
Страница 20: ...20 Rockwell Automation Publication 750 PM101B EN P April 2022 Chapter 2 Parameter Organization Notes ...
Страница 118: ...118 Rockwell Automation Publication 750 PM101B EN P April 2022 Chapter 4 Troubleshooting Notes ...
Страница 122: ...122 Rockwell Automation Publication 750 PM101B EN P April 2022 Appendix A Permanent Magnet Motors Notes ...
Страница 126: ...126 Rockwell Automation Publication 750 RM100B EN P August 2021 ...