1-2
Installation/Wiring
PowerFlex Diode Bus Supply User Manual
Publication 20T-UM001D-EN-P
Minimum Mounting
Clearances
Ambient Operating Temperatures
The Diode Bus Supply is designed to operate at 0…40 °C (32…104 °F)
ambient without derating. Remove the label from the top to operate the
Diode Bus Supply in ambients 41 °C up to 50 °C (104 °F up to 122 °F).
Important: Removing the adhesive label changes the enclosure rating from
NEMA Type 1 Enclosed to Open Type. This also changes the
side-to-side mounting clearance requirement.
Ensure that proper cooling is provided to the Diode Bus Supply to stay
under the 40 °C rated specification. Add exhaust fans to the front or top of
the enclosure bay and provide a filtered opening at the bottom of the cabinet
bay.
The Diode Bus Supply watt loss (from specification section) is 500 W at
120 A. The three-phase AC line reactor watt losses are listed in the 1321
Power Conditioning Products Technical Data, publication
It is recommended that the system integrator completes a thermal evaluation
to ensure adequate cooling to maintain proper operating conditions for each
cabinet or bay.
100 (4)
100 (4)
100 (4)
100 (4)
50 (2)
50 (2)
No Adhesive Label on Top
With Adhesive Label on Top
Dimensions are in millimeters and (inches).
for detailed dimension information.
Содержание Allen-Bradley PowerFlex 4M
Страница 1: ...PowerFlex Diode Bus Supply User Manual ...
Страница 4: ...soc ii Summary of Changes PowerFlex Diode Bus Supply User Manual Publication 20T UM001D EN P Notes ...
Страница 12: ...P 6 Overview PowerFlex Diode Bus Supply User Manual Publication 20T UM001D EN P Notes ...
Страница 30: ...2 4 Start Up Troubleshooting PowerFlex Diode Bus Supply User Manual Publication 20T UM001D EN P Notes ...
Страница 36: ...A 6 Supplemental Information PowerFlex Diode Bus Supply User Manual Publication 20T UM001D EN P Notes ...
Страница 38: ...B 2 History of Changes PowerFlex Diode Bus Supply User Manual Publication 20T UM001D EN P Notes ...
Страница 41: ......