3-8
Programming and Parameters
Basic Program Group
Stop drive before changing this parameter.
P031 [Motor NP Volts]
Set to the motor nameplate rated volts.
Values
Default
Based on Drive Rating
Min/Max:
20/Drive Rated Volts
Display:
1 VAC
Stop drive before changing this parameter.
P032 [Motor NP Hertz]
Related Parameter(s):
Set to the motor nameplate rated frequency.
Values
Default
60 Hz
Min/Max:
10/240 Hz
Display:
1 Hz
P033 [Motor OL Current]
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60
seconds or 200% for 3 seconds.
Values
Default
Based on Drive Rating
Min/Max:
0.0/(Drive Rated Amps
×
2)
Display:
0.1 Amps
P034 [Minimum Freq]
Sets the lowest frequency the drive will output continuously.
Values
Default
0.0 Hz
Min/Max:
0.0/240.0 Hz
Display:
0.1 Hz
Stop drive before changing this parameter.
P035 [Maximum Freq]
Sets the highest frequency the drive will output.
Values
Default
60 Hz
Min/Max:
0/240 Hz
Display:
1 Hz
userman.book Page 8 Friday, June 21, 2002 2:48 PM
Содержание Allen-Bradley PowerFlex 4
Страница 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Страница 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Страница 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Страница 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Страница 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Страница 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Страница 93: ...userman book Page 1 Friday June 21 2002 2 48 PM ...