Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
49
Access Procedures
Chapter 3
Open and Close the Control
Panel
Open the Control Panel
Opening the control panel provides access to the armature leg fuses, overvoltage
clipping board, SCR gate lead terminals, SCR modules, bimetal thermostat,
discharge resistors, and inrush limiting resistors.
1.
Read the General Safety Precautions on page
.
2.
Remove power from the drive. See Remove Power from the Drive on page
.
3.
Disconnect the DPI cable from the HIM (if present).
4.
Insert a flathead screwdriver into the holes in the right side of the
protective covers on the drive and turn the latch 90° counter-clockwise.
5.
Open the control panel to the left.
Close the Control Panel
Close the control panel in the reverse order.