Publication 2711P-UM001D-EN-P - September 2005
Troubleshooting
8-11
Startup Information
Messages
The table provides a list of system information messages that display
at startup. The messages are in the order that they appear on the
terminal screen during startup and typically display for a few seconds.
The messages apply to all terminals except where indicated.
Startup information messages show the startup sequence of the
terminal but do not require that you perform any action.
Message #
Displayed Message
Description
37
Video Initialized
Configures and initializes the graphics video system.
30
Watchdog Test
Tests the watchdog circuitry to verify system integrity.
1
RAM Test
Tests the RAM memory.
31
Stuck Key
Checks the integrity of the function key hardware.
31.5
Stuck Touch
Checks the integrity of the touch screen hardware.
32
Battery Test
Checks the integrity of the battery hardware.
2.5
Registry Search
Locates and loads the most recent, valid registry. Multiple copies of the registry are
maintained. If power is lost during a registry update, a valid registry is available the next
time power is applied to the terminal.
2
Image Search
Checks for new OS firmware upgrade on the external compact flash card and the serial port.
11
(1)
Downloading Image
Downloads a new OS firmware upgrade to internal RAM. Message may remain on screen
for several minutes.
50
External CF
Transfers a new OS firmware upgrade from the external compact flash card to the terminal.
Message may display for several minutes.
20
Transfer Image
Programs the OS firmware just downloaded into RAM. Message may remain on screen for
several minutes.
23
(2)
Internal CF
Programs the OS firmware just downloaded into the internal flash memory. Message may
display for several minutes.
24
CRC Check
Checks the integrity of the OS firmware.
27
Decompress System
Decompresses the compressed OS firmware into RAM.
28
Starting System
Launches the operating system (OS).
29
System Check ###
Internal file system integrity check (### is percent progress indicator).
29.1
System Check
Internal file system integrity check disabled. Contact technical support.
(1)
The status number and message displays only on the 400 and 600 terminals.
(2)
The status number and message displays only on the 700-1500 terminals.
Содержание Allen-Bradley PanelView Plus 400
Страница 1: ...PanelView Plus Terminals 2711P 400 600 700 1000 1250 1500 User Manual...
Страница 6: ...Publication 2711P UM001D EN P September 2005 Table of Contents iv...
Страница 44: ...Publication 2711P UM001D EN P September 2005 2 16 Installation...
Страница 56: ...Publication 2711P UM001D EN P September 2005 3 12 Connect Power...
Страница 160: ...Publication 2711P UM001D EN P September 2005 7 12 Transfer files and Upgrade Firmware...
Страница 176: ...Publication 2711P UM001D EN P September 2005 8 16 Troubleshooting...
Страница 182: ...Publication 2711P UM001D EN P September 2005 B 2 Compatible USB Devices...
Страница 191: ...Publication 2711P UM001D EN P September 2005 Index 5...
Страница 192: ......