Terminal Connections
DeviceNet Network (NET) Status Indicator
This bi-color (green/red) LED indicates the status of the
communication link.
Condition
Status
Indication
off
not powered
Device is not online.
not online
The device has not completed the
Dup_MAC_ID test yet.
The device may not be powered; look
at the Module Status LED.
flashing green
(1)
(1)
The flash rate of the LED is approximately 1 flash per second. The LED should be on for approximately 0.5
seconds and off for approximately 0.5 seconds.
online
Device is online, but has no
connections in the established state.
not connected
The device has passed the
Dup_MAC_ID test, is online, but has
no established connections to other
nodes.
green
link okay, online, connected
The device is online and has
connections in the established state.
flashing red
connection timeout
One or more I/O connections are in
the timed-out state.
red
critical link failure
Failed communication device. The
device has detected an error that has
rendered it incapable of
communicating on the network
(Duplicate MAC ID or Bus-off).
Check network integrity and baud
rate of all devices. Then cycle power
to the card by shutting down and
cycling power to your computer.
ATTENTION
Extensive use of Change-of-State connections,
particularly with rapidly changing data, can adversely
impact the available DeviceNet network bandwidth.
If the network bandwith becomes consumed, some
devices may only be able to communicate
intermittently. This can result in timeout errors and
possible loss of data. If timeouts occur, consider
changing the connection type for some of the
Change-of-State connections to Cyclic or Polled.
Содержание Allen-Bradley PanelView Plus 400
Страница 1: ...PanelView Plus Terminals 2711P 400 600 700 1000 1250 1500 User Manual...
Страница 6: ...Publication 2711P UM001D EN P September 2005 Table of Contents iv...
Страница 44: ...Publication 2711P UM001D EN P September 2005 2 16 Installation...
Страница 56: ...Publication 2711P UM001D EN P September 2005 3 12 Connect Power...
Страница 160: ...Publication 2711P UM001D EN P September 2005 7 12 Transfer files and Upgrade Firmware...
Страница 176: ...Publication 2711P UM001D EN P September 2005 8 16 Troubleshooting...
Страница 182: ...Publication 2711P UM001D EN P September 2005 B 2 Compatible USB Devices...
Страница 191: ...Publication 2711P UM001D EN P September 2005 Index 5...
Страница 192: ......