5/25/2018
530800 - Fuse and Line Filter sizing for the Kinetix 5500 drive
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/530800
3/10
Shown are quantity 5, 2198-H008-ERS modules all with AC Sharing from the same AC power source. The 2198-
H008-ERS continuous AC line Amps are 2.60 Amps RMS continuous.
Recommended Components for the AC Sharing system are:
For the above example using 5 2198-H008-ERS use KTK-R-15 fuses. Other recommended fusing can be
found in the
Kinetix Servo Drive Technical Documentation
(http://gmc-td003_-en-p.pdf/).
With AC sharing, ALL converters must be of the same power therefore all axis must be the same. In AC
Sharing, you could not use 3, 2198-H008-ERS and 2, 2198-H015-ERS. This is due to different AC line
characteristics such as inrush in order to have a symmetrical AC power up.
AC Sharing configuration does not support use of the 2198 capacitor module for similar reasons as item 2
above.
For a line filter use, the total AC amps is approximately 13 Amps RMS for this configuration. A 2198-DB08-F
is 7.5 Amps continuous and cannot be used. Therefore, use 2198-DB20-F as that can handle the current
requirements of the AC Sharing configuration shown above.
AC Sharing MUST be used with both AC sharing bus bar and DC control power bus bars.
Three phase power MUST be used for AC/DC Sharing. Single Phase operation is not supported in AC/DC
Sharing.
AC Bus bar and DC control power bus bars MUST be used in this configuration.
The 2198-H008-ERS is a frame 1 Kinetix 5500, as referenced in the
Kinetix 5500 User Manual
(http://literature.rckwellautomation.com/idc/groups/literature/documents/um/2198-um001_-en-p.pdf) &
Kinetix