Rockwell Automation Publication 1503-UM053C-EN-P - March 2015
25
Installation and Wiring
Chapter 3
Figure 11 - Three-Wire Control
Figure 12 - Timing Diagram 400A (Electrically Held) Contactor for IntelliVAC Control with three-
wire Control
MOV
3
2
1
EC
-
+
4
TCO
12
11
AUX
CCO
5
6
L1
L2/N
G
+ -
M-IV
9
10
M-IV
15
16
M
M-IV
M
Control Power
Control Power Fuse
*
*
See
Table 5 on page 19
for recommended fuse sizing.
Capacitor
(Optional)
Emergency Stop
(when required)
Overload
Stop
Start
Close
Contactor
Status
15ms
200ms
90ms
(@120VAC)
80ms
60ms
5ms
30ms
15ms
Close Command
to Micro
Micro Output
to close coil
Close level of current
to close coils
Contactor status
relay output
Module status
relay output
Contactor auxiliary
input to micro
Contactor pick up
Debounce
Debounce
Clamp delay
Acknowledge window
Natural contactor drop out
Selectable drop out time
(0 …190 ms)
*
Contact status relay closes on request to close. It will open if the contactor does not close withing 200 ms and module will
fault (opening module status relay).
**
For this example, the 130 ms drop-out time has been selected. The drop-out time is 50 ms. The micro controller delay is
130-50=80 ms.
*
**
Содержание Allen-Bradley IntelliVAC 1503VC-BMC5
Страница 1: ...IntelliVAC Contactor Control Module Catalog Number Bulletin 1503VC Series E User Manual...
Страница 6: ...6 Rockwell Automation Publication 1503 UM053C EN P March 2015 Summary of Changes Notes...
Страница 14: ...14 Rockwell Automation Publication 1503 UM053C EN P March 2015 Chapter 2 Receiving andStorage Notes...
Страница 40: ...40 Rockwell Automation Publication 1503 UM053C EN P March 2015 Chapter 6 Spare Parts Notes...
Страница 45: ......