Rockwell Automation Publication 440R-IN084A-EN-P - July 2022

3

Minotaur MSR117T Safety Relay Installation Instructions

Figure 4 - Example 3

Single channel gate interlock, automatic reset, monitored output expansion with 
MSR132.

Figure 5 - Example 4

Single channel E-stop, manual reset, dual channel monitored output.

Circuit Diagram

Figure 6 - Diagram

Approximate Dimensions

Figure 7 - Dimensions [mm (in.)]

Safety Specifications

The MSR117T safety relay can be used in safety circuits according to 
DIN EN 60204-1/VDE 0113 part 1. Safety requirements that are specified in 

Specification on page 1

 are maximum, based on the operation mode and wiring.

Specifications are applicable only if the safety function is demanded at least once 
within 6 months. Conduct all diagnostic tests at least before the next demand, as 
mission time (TM) the proof test interval (PTI) is assumed. Components failure 
rates are according to SN29500.

Figure 8 - Safety Circuit

Declaration of Conformity

CE Conformity

Rockwell Automation declares that the products that are shown in this document 
conform with the Essential Health and Safety Requirements (EHSRs) of the 
European Machinery Directive (2006/42/EC) and EMC Directive 2014/30/EU.

For a comprehensive CE certificate visit: 

rok.auto/certifications

.

UKCA Conformity

Rockwell Automation declares that the products that are shown in this document 
are in compliance with the Supply of Machinery (Safety) Regulations (2008 No. 1597) 
and Electromagnetic Compatibility Regulations (2016 No. 1091).

For a comprehensive UKCA certificate visit: 

rok.auto/certifications

.

Table 1 - Circuit Diagram Explanation

Abbreviation

Description

A1, A2

Power

13, 23, 33, 14, 24, 34 Safety output (N.O.)

X1, X2

Monitoring feedback loop incorporating reset button

41, 42

Auxiliary output (N.C.)

PWR

Status indicator illuminates green when the unit is powered, flashing 
green if cross-loop faults occur

Status indicator illuminates when K1 and K2 is closed

Open

Ground

Closed

Open

Ground

Reset

Overvoltage protection 

24V DC Supply

Reset

(a)

(a)

Example

Channel 1

Channel 2

Sensor 

Contact

Sensor 

Contact

E-stop 800F 

(a)

Actuator 1

Actuator 2

Safety Relay 440R

Contactor 100S 

(a)