Rockwell Automation Publication 440G-UM001C-EN-P - June 2019
27
Chapter
5
Commissioning
The 440G-LZ safety switch is available with standard coded actuators or
unique coded actuators.
• Switches with standard coded actuators are ready for use and do not
require commissioning.
• Switches with unique coded actuators need to be commissioned before
use. The actuator teach process is not performed at the factory and must
be performed when the switch is first put into use. After the first-time
learn, this process can be repeated up to seven more times with unique
coded replacement actuators.
Set-up
During commissioning, connect the switch as shown in
Figure 10
:
• Connect brown wire (PWR) to 24V DC.
• Connect blue wire (GND) to 0V DC.
• Connect red wire (Safety A+) and yellow wire (Safety B+) to 24V DC.
• Connect green wire (Lock Command) to 24V DC.
• Safety A (gray) and Safety B (pink) — optional, no connection required
during commissioning
• Aux (white) — optional, no connection required during commissioning
IMPORTANT
When the switch learns a new actuator, it no longer recognizes previously
learned actuators.
Содержание Allen-Bradley Guardmaster 440G-LZS21SP Series
Страница 26: ...26 Rockwell Automation Publication440G UM001C EN P June 2019 Chapter 4 Wiring Notes ...
Страница 36: ...36 Rockwell Automation Publication440G UM001C EN P June 2019 Chapter 6 Diagnostics andTroubleshooting Notes ...
Страница 52: ...52 Rockwell Automation Publication440G UM001C EN P June 2019 Chapter 7 Application Examples Notes ...
Страница 60: ...60 Rockwell Automation Publication440G UM001C EN P June 2019 Appendix B Typical Installations Notes ...
Страница 61: ...Rockwell Automation Publication440G UM001C EN P June 2019 61 Typical Installations Appendix B Notes ...
Страница 62: ...62 Rockwell Automation Publication440G UM001C EN P June 2019 Appendix B Typical Installations ...
Страница 63: ......