Figure 7 - Mechanical Latch Dimensions (Optional)
For mechanically latched contactors, the manual trip button in the cabinet
door must be in line with the trip lever on the contactor.
Electrical Connections
A wire harness connects the control wiring to the contactor from the low
voltage control panel. The harness connects to a keyed wire plug on the lower
left side of the contactor (plug configurations vary by contactor type). If the
contactor is supplied as an OEM component for installation in a custom
application, the following two control options and a connecting wire harness
are available from Rockwell Automation.
•
IntelliVAC control module
•
Electromechanical control panel
Connect incoming medium voltage power to the line side terminals at the top,
rear of the contactor near the control fuse clips. Use 3/8 in. (10 mm) bolts
torqued to 20 lb
•
ft (292 N
•
m) to secure the connection.
Connect outgoing medium voltage power to the load side terminals halfway
down the rear of the contactor. Use 3/8 in. (10 mm) bolts torqued to 20 lb
•
ft
(292 N
•
m) to secure the connection.
2 . 9 3
1 . 5 3
Contactor
Содержание Allen-Bradley G Series
Страница 1: ...Medium Voltage 450 A Contactor Series G Bulletin Number 1502 User Manual Original Instructions ...
Страница 6: ...6 Rockwell Automation Publication 1502 UM060A EN P October 2020 Notes ...
Страница 16: ...16 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 1 Product Description Notes ...
Страница 20: ...20 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 2 Receiving and Handling Notes ...
Страница 48: ...48 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 4 Maintenance Notes ...
Страница 50: ...50 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 5 Troubleshooting Notes ...