Rockwell Automation Publication 2100-IN012D-EN-P - September 2010
95
Chapter
10
Maintenance After Fault Condition
Maintain the MCC After a
Fault Condition
The opening of the short circuit protective device (such as fuses or circuit
breakers) in a properly coordinated motor branch circuit is an indication of a
fault condition in excess of operating overload and must be corrected.
Fault conditions can cause damage to control equipment. When a fault occurs,
follow this procedure.
1.
De-energize the MCC.
2.
Investigate the cause of the fault and inspect all equipment thoroughly per
NEMA Standards publication ICS 2.3-1995, Instructions for the handling
installation operator and maintenance of MCCs not rated more than
600V, Section 11, Maintenance after a Fault has Occurred.
3.
Make necessary repairs to units, components and structures as required,
prior to reenergizing the equipment.
Be sure that replacement parts are suitably rated for the application.
An insulation resistance test (megger) may be required. Refer to
.
ATTENTION:
Make sure that the MCC remote power sources are
disconnected and that the respective disconnects are locked in the OFF/O
position.
Содержание Allen-Bradley CENTERLINE 2100
Страница 1: ...Installation Instructions CENTERLINE 2100 Low Voltage Motor Control Centers Catalog Number 2100 ...
Страница 4: ...4 Rockwell Automation Publication 2100 IN012D EN P September 2010 Summary of Changes Notes ...
Страница 22: ...22 Rockwell Automation Publication 2100 IN012D EN P September 2010 Chapter 1 General Information Notes ...
Страница 98: ...98 Rockwell Automation Publication 2100 IN012D EN P September 2010 Chapter 11 Renewal Parts Notes ...
Страница 106: ...106 Rockwell Automation Publication 2100 IN012D EN P September 2010 Index ...
Страница 107: ......