Rockwell Automation Publication 750COM-UM100A-EN-P - June 2021
15
Chapter
3
Troubleshooting
Status Indicators
The TLink option module has four light-emitting diode (LEDs) used to signal
the following events:
DS1
:
•
Red continuous when the fiber-optic cable is disconnected (receiver
side).
•
Green continuous when fiber-optic cable is connected (receiver side).
•
Green blinking when packets are incoming (transmission is on).
DS2
:
•
Green continuous: TLink module role is Leader. Transmitting is enabled.
•
Green blinking: Transmission (packets are being transmitted, TLink role:
leader).
•
Off: The TLink is not configured as a leader
DS3
:
•
On (green): External power supply connected
•
Off: external power supply not connected
DS4
:
•
Green blinking: TLink FPGA is powered on, normal operation
•
Red blinking: TLink FPGA detected an unexpected condition during
communication/operation. Card status is sent to drive.
DS1 DS2 DS3 DS4
Transceiver Cage
Edge Connector
Receive
Transmit
Plug for
Optional 24V
Power Supply