1
Publication 193-UM010A-EN-P – January 2008
Appendix
A
Specifications
Terminal Ratings:
Terminal Screw
M3
Wire Cross Section
See wiring diagram section
Torque
0.5…0.6 N•m (4.4…5.3 lb.-in)
Degree of Protection
IP20
Power Supply Ratings
:
Rated Supply Voltage
Us
24V DC
Rated Operating Range
Ue
20.4 - 26.4
Rated Supply Current
Ie
0.1 A
Maximum Surge Current at Power-Up
2.5 A
Maximum Power Consumption
2.5 W
Maximum Power Interruption Time
0.5ms
Output Relay Ratings:
Terminals
OUT A:
13/14
Type of Contacts
Form A
SPST - NO
Rated Thermal Current
I
the
5 A
Rated Insulation Voltage
Ui
300V AC
Rated Operating Voltage
Ue
240V AC
Rated Operating Current
Ie
3 A (at 120V AC), 1.5 A (at 240V AC)
0.25 A (at 110V DC), 0.1 A (at 220V DC)
Minimum Operating Current
10 mA at 5V DC
Rating Designation
B300
Utilization Category
AC-15
Resistive Load Rating
(p.f.=1.0)
5 A, 250V
AC
5 A, 30V DC
Inductive Load Rating
(p.f.=0.4), (L/R=7 ms)
2 A, 250V AC
2 A, 30V DC
Short Circuit Current Rating
1,000 A
Recommended Control Circuit Fuse
KTK-R-6
(6 A, 600V)
Rated Number of Operations
Out A:
W/100-C-09…100-C43
W/100-C-60…100-C85
W/NEMA Size 0…2
W/NEMA Size 3
5,000,000
2,500,000
1,000,000
300,000
Input Ratings:
Terminals
IN 1:
IN 2:
SSV (Sensor Supply Voltage)
1
2
3
Supply Voltage (provided by module)
20.4 - 26.4V DC