Rockwell Automation Allen-Bradley 193-EPRB Скачать руководство пользователя страница 11

Publication 193-UM010A-EN-P – January 2008

Protection Functions        

2-3

The PROFIBUS Module will command the E1 Plus Overload Relay to trip if all the following 
conditions are met:

No trip currently exists

Jam Protection

 is enabled

Jam Inhibit Time

 has expired

The motor current is greater than the 

Jam Trip Level

 for a time period greater than the 

Jam Trip Delay

When the conditions for a jam trip are satisfied, the following will occur:

Bit 2 in Parameter 3, 

Trip Status

, will go to “1”

Bit 0 in Parameter 5, 

Device Status

, will go to “1”

The E1 Plus Overload Relay's trip relay contacts (95 and 96) will open

Out A will be placed in their Protection Fault State (if so programmed)

Jam Warning

Parameter 16, 

Jam Warn Level

, allows the installer to define the current at which the PROFIBUS 

Module will indicate a warning. It is user-adjustable from 100…600% FLA.
The PROFIBUS Module will indicate a Jam warning if:

No warning currently exists

Jam Warning is enabled

Jam Inhibit Time has expired

The motor current is equal to or greater than the Jam Warn Level

When the Jam Warning conditions are satisfied, the following will occur:

Bit 2 in Parameter 4, 

Warning Status

, will go to “1”

Bit 1 in Parameter 5, 

Device Status

, will go to “1”

Underload Protection

Motor current less than a specific level may indicate a mechanical malfunction in the installation, 
such as a torn conveyor belt, damaged fan blade, broken shaft, or worn tool. Such conditions 
may not harm the motor, however, rapid detection may help to minimize equipment damage 
and loss of production.

IMPORTANT

The Protection Fault State of OUT A is defined by parameter 22 
(

OUTA Pr FltState

) and parameter 23 (

OUTA Pr FltValue

).

IMPORTANT

The jam inhibit timer starts after the load current transitions from 0 A to 
30% FLA. The PROFIBUS Module does not begin monitoring for a jam 
condition until the 

Jam Inhibit Time

 expires.

IMPORTANT

The Jam Warning function does not include a time delay feature. Once 
the 

Jam Inhibit Time

 has expired, the Jam Warning indication is 

instantaneous.

Содержание Allen-Bradley 193-EPRB

Страница 1: ...USER MANUAL BULLETIN 193 E1 Plus PROFIBUS Module CATALOG NUMBER 193 EPRB...

Страница 2: ...ssume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or s...

Страница 3: ...d Protection 2 3 Underload Warning 2 4 Communication Fault Protection 2 4 Comm Fault Warning 2 4 Communication Idle Protection 2 4 Comm Idle Warning 2 5 Chapter 3 PROFIBUS Configuration Introduction 3...

Страница 4: ...s 4 3 Input and Output Troubleshooting Procedures 4 6 Trip and Warning Troubleshooting Procedures 4 8 Appendix A Specifications A 1 Appendix B PROFIBUS Information Structure of the Set Prm Data telegr...

Страница 5: ...document is to serve as a guide for proper installation The National Electrical Code and any other governing regional or local code will take precedence Rockwell Automation cannot assume responsibili...

Страница 6: ...tion Figure 1 2 Installation 1 Figure 1 3 Installation 2 Figure 1 4 Installation 3 PROFIBUS Connector Network Status LED Power Supply Connector I O Connector 2 Driver 0 7 1 1 N m 6 10 lb in 7mm 28 in...

Страница 7: ...m Table 1 1 Wire and Size Torque Specifications 1X 2X 24 12 AWG 24 16 AWG 5 lb in 1X 2X 0 2 2 5 mm2 0 25 1 mm2 0 55 N m 1X 2X 0 2 2 5 mm2 0 2 1 mm2 0 55 N m OUTA B300 13 14 1 2 3 SSV IN2 IN1 A1 A2 20...

Страница 8: ...193 EE_B mm in 67 2 64 148 5 83 85 2 3 35 24 5 96 13 9 55 35 1 38 60 2 36 86 5 3 40 2 08 4 5 17 22 86 100 C30 C37 193 EE_D mm in 67 2 64 148 5 83 101 2 3 98 24 5 96 13 9 55 35 1 38 60 2 36 104 4 09 2...

Страница 9: ...available for resetting a tripped E1 Plus Overload Relay with a PROFIBUS module Blue mechanical reset button located on the front of the E1 Plus Overload Relay Setting Parameter 19 Trip Reset to Reset...

Страница 10: ...ed gear These conditions can result in overheating of the motor and equipment damage Rapid jam fault detection helps to minimize damage and loss of production By continuously monitoring the motor curr...

Страница 11: ...ning currently exists Jam Warning is enabled Jam Inhibit Time has expired The motor current is equal to or greater than the Jam Warn Level When the Jam Warning conditions are satisfied the following w...

Страница 12: ...Module and a PROFIBUS network can result in the loss of application control and or critical process diagnostic data Rapid communication fault detection helps minimize potential damage due to uncontro...

Страница 13: ...indicate a Comm Idle warning if No warning currently exists Comm Idle Warning is enabled The PROFIBUS module is in idle clear mode When the Comm Idle warning conditions are satisfied the following wil...

Страница 14: ...Publication 193 UM010A EN P January 2008 2 6 Protection Functions...

Страница 15: ...module to the network configuration GSD modules can be added i e mapped as Cyclic I O as needed in any order with a few restrictions At least one byte must be mapped as Cyclic I O This can either be d...

Страница 16: ...le as follows Table 3 1 Control Register contents Bit 0 OutA Control of the Output relay The bit is flank triggered i e a state transition from 0 to 1 or from 1 to 0 must be performed to change the st...

Страница 17: ...O has been performed The bit can be cleared again by clearing the Save bit in the Control Register Bit 7 Motor Current Same functionality as bit 5 in parameter 5 Device Status Parameter Programming Pr...

Страница 18: ...ip Log 1 3 Trip Status 10 Single Three Ph 21 Set to Defaults 24 OutA Pb FltState 32 Trip Log 2 4 Warning Status 11 OL Reset Mode 25 OutA Pb FltValue 33 Trip Log 3 5 Device Status 12 OL Warning Level 2...

Страница 19: ...parameter provides warning identification 1 Warning 0 No Warning Access Rule Read Size 2 bytes Group Monitor Units Min Value Max Value Default Value None Bit Function 15 14 13 12 11 10 9 8 7 6 5 4 3 2...

Страница 20: ...65535 Default Value None Serial Number Index No 7 This parameter reports the serial number assigned during production of the PROFIBUS Module Access Rule Read Size 4 bytes Group Monitor Units Min Value...

Страница 21: ...ree phase application This parameter should be set to Single Phase when Bulletin 193S or 592S devices are employed Access Rule Read Write Size 1 byte Group Advanced Setup Units Min Value 0 Single Phas...

Страница 22: ...Write Size 1 byte Group Advanced Setup Units Seconds Min Value 0 5 Max Value 25 0 Default Value 5 0 Jam Trip Level Index No 15 This parameter sets the jam trip level Access Rule Read Write Size 2 byte...

Страница 23: ...Lock Units Min Value 0 Ready Max Value 1 Reset Trip Default Value 0 Program Lock Index No 20 This parameter prohibits the device parameters from being altered when set to Locked It must be set to Unlo...

Страница 24: ...S network fault occurs When set to 1 Output A will hold the state prior to PROFIBUS fault occurrence When set to 0 Output A will open or close as determined by the setting of Parameter 25 Access Rule...

Страница 25: ...Max Value 0 Normal 1 Trip reset 2 OL Contact Default Value 0 IN2 Assignment Index No 29 This parameter allows the user to assign a specific function to the discrete IN2 inputs Access Rule Read Write S...

Страница 26: ...Value None Trip Log 4 Index No 34 This parameter records the trip previous to Trip Log 3 Access Rule Read Size 2 bytes Group Trip History Units Min Value See Trip Status table Max Value See Trip Stat...

Страница 27: ...her enter the Configuration Error Mode ATTENTION Servicing energized industrial control equipment can be hazardous Electrical shock burns or unintentional actuation of controlled industrial equipment...

Страница 28: ...ng using NETWORK STATUS LED Color State Possible Cause Corrective Action None 1 The E1 Plus PROFIBUS Module is not receiving power at the PROFIBUS connector 2 The module is off line Check power and PR...

Страница 29: ...he parameter and retry 0xB7 Invalid Range X The value in the service request was outside the specified range Correct the value in the service request and retry 0xC0 Read constrain conflict X The lengt...

Страница 30: ...Remove control circuit power and check the control circuit fuse and the control wiring to the E1 Plus PROFIBUS Module output terminals 4 Check the OUTA Pr FltState Pr FltValue Pb FltState Pb FltValue...

Страница 31: ...rrent Ithe 5 A Rated Insulation Voltage Ui 300V AC Rated Operating Voltage Ue 240V AC Rated Operating Current Ie 3 A at 120V AC 1 5 A at 240V AC 0 25 A at 110V DC 0 1 A at 220V DC Minimum Operating Cu...

Страница 32: ...Pollution Environment Pollution Degree 2 Terminal Marking EN 50012 Degree of Protection IP20 Electromagnetic Compatibility Electrostatic Discharge Immunity Test Level Performance Criteria 8 kV Air Di...

Страница 33: ...Acyclic services No Set Slave Address SSA support Yes Jam Protection Trip Level 150 600 FLA Trip Delay 0 1 25 0 sec Inhibit 0 250 sec Standards UL 508 CSA 22 2 No 14 EN 60947 4 1 1 Performance Criteri...

Страница 34: ...Publication 193 UM010A EN P January 2008 A 4 Specifications...

Страница 35: ...ue for parameter 9 Warning Enable 8 Single Three Ph Initial value for parameter 10 Single Three Ph 9 OL Reset mode Initial value for parameter 11 OL Reset mode 10 OL Warning Level Therm Util Initial v...

Страница 36: ...er If successful the new node address will be stored in non volatile memory replacing the previous value of parameter 35 SSA Node Address NOTE This service will be rejected if a previous SSA service r...

Страница 37: ...ize Default Value Manufacturer ID 2 octets 0x0002 Order ID 20 octets 193 EPRB Serial Number 16 octets assigned during manufacturing Hardware Revision 2 octets assigned during manufacturing Software Re...

Страница 38: ...e If you experience a problem with a hardware module within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Sup...

Страница 39: ......

Страница 40: ...Publication 193 UM010A EN P January 2008 Copyright 2008 Rockwell Automation Inc All Rights Reserved Printed in USA...

Отзывы: