![Rockwell Automation Allen-Bradley 1718-A10 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-1718-a10/allen-bradley-1718-a10_installation-instructions-manual_1475238004.webp)
4
Rockwell Automation Publication 1718-IN001A-EN-E - June 2020
1718 Ex I/O
European Hazardous Location Approval
The following applies to products marked
II 2(1)G. Such modules:
• Are Equipment Group II, Equipment Category 2, and comply with the Essential Health and Safety
Requirements relating to the design and construction of such equipment given in Annex II to
Directive 2014/34/EU. For details, see the EU Declaration of Conformity from the 1718
Certification Bulletin, publication
1718-CT001
.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or
air are likely to occur in normal operation occasionally (see Zone 1 definition). Such locations
correspond to Zone 1 classification according to ATEX directive 2014/34/EU.
• The I/O modules have outputs leading into Category 1
[Zone 0 (gas) or Zone 20 (dust)] or Category M1 (mining)].
1718-CF4H
• Field connections and mounting: the type of protection is "II 2(1) G Ex db eb q [ia Ga] IIC Gb" and
"II (1) D [Ex ia Da] IIIC", comply to Standards EN 60079-0:2012/A11:2013, EN 60079-1:2014, EN
60079-5:2015, EN 60079-7:2015 and EN 60079-11:2012. Certificate Presafe 19 ATEX 14057 U.
1718- IF4HB
• Field connections and mounting: the type of protection is "II 2(1) G Ex db eb q [ia Ga] IIC Gb" and
"II (1) D [Ex ia Da] IIIC", comply to Standards EN 60079-0:2012/A11:2013, EN 60079-1:2014, EN
60079-5:2015, EN 60079-7:2015 and EN 60079-11:2012. Certificate Presafe 19 ATEX 14056 U.
1718-IR4B, 1718-IT4B, 1718-IBN8B, 1718-IJ
• Field connections and mounting: the type of protection is "II 2(1) G Ex db eb q [ia Ga] IIC Gb" and
"II (1) D [Ex ia Da] IIIC", comply to Standards EN 60079-0:2012/A11:2013, EN 60079-1:2014, EN
60079-5:2015, EN 60079-7:2015 and EN 60079-11:2012. Certificate Presafe 19 ATEX 14058 U.
1718-IBN8
• Field connections and mounting: the type of protection is "II 2(1) G Ex db eb q [ia Ga] IIC Gb" and
"II (1) D [Ex ia Da] IIIC", comply to Standards EN 60079-0:2012/A11:2013, EN 60079-1:2014, EN
60079-5:2015, EN 60079-7:2015 and EN 60079-11:2012. Certificate Presafe 19 ATEX 14055 U.
1718-OB2, 1718-OB2L
• Field connections and mounting: the type of protection is "II 2(1) G Ex db eb q [ia Ga] IIC Gb" and
"II (1) D [Ex ia Da] IIIC", comply to Standards EN 60079-0:2012/A11:2013, EN 60079-1:2014, EN
60079-5:2015, EN 60079-7:2015 and EN 60079-11:2012. Certificate Presafe 19 ATEX 14054 U.