20
Rockwell Automation Publication 1718-IN001A-EN-E - June 2020
1718 Ex I/O
Requirements for wires, stranded conductors, and wire end ferrules.
IMPORTANT
Use the terminal blocks from the range of accessories. For more
information, see Accessories in Chapter 1 of the 1718 Ex I/O User Manual,
publication
.
WARNING:
A spark can be generated by bare, conductive parts such as loose wire
ends, which can cause explosive mixtures to ignite.
• Stranded conductors must always be used with wire end ferrules. We recommend
using wire end ferrules approved according to DIN 46228-4.
Wires
Description
Value
Insulation stripping
9 mm (0.35 in.)
Core cross-section (conductor):
0.14…0.5 mm
2
(26…20 AWG) for 1718-IBN8
0.08…1.5 mm
2
(28…16 AWG) for all other modules
External diameter (con insulation)
2…3 mm (0.078…0.118 in.)
Stranded conductors
Description
Value
Insulation stripping
9 mm (0.35 in.)
Core cross-section for wire end ferrules with plastic sleeve
0.5 mm
2
according to IEC 60228 Class 5 and 6
Core cross-section for wire end ferrules without plastic sleeve
0.5…1.5 mm
2
according to IEC 60228 Class 5 and 6