10
Rockwell Automation Publication 1606-RM101A-EN-P - July 2020
Output
Figure 10 - Short-circuit on Output, Hiccup
PLUS
Mode, Typ
Attributes
Values
Notes
Output voltage
Nom
24V
—
Adjustment range
Min 24…28V
Guaranteed
value
Max 30.0V
This is the max output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is
not guaranteed that this value can be achieved.
Factory settings
Typ
24.1V
±0.2%, at full load and cold unit
Line regulation
Max
10 mV
85…300V AC
Load regulation
Max
50 mV
0…12 A, static value, see
Ripple and noise voltage
Max
50 mVpp
Bandwidth 20 Hz…20 MHz, 50 Ω
Output current
Nom
12 A
(1)
At 24V and an ambient temperature below 45 °C (113 °F), see
Nom
10 A
At 24V and 60 °C (140 °F) ambient temperature, see
Nom
7.5 A
At 24V and 70 °C (158 °F) ambient temperature, see
Nom
10.3 A
At 28V and an ambient temperature below 45 °C (113 °F), see
Nom
8.6 A
At 28V and 60 °C (140 °F) ambient temperature, see
Nom
6.45 A
At 28V and 70 °C (158 °F) ambient temperature, see
Typ 30
A
For minimal 12 ms once every 5 seconds, see
.The output voltage stays above 20V. See
for more peak current measurements. For AC 100V mains, the pulse length is shorter than 12 ms.
Overload behavior
—
Continuous current
Output voltage above 13V DC, see
—
Hiccup
PLUS
mode
(2)
Output voltage below 13V DC, see
Short-circuit current
Min
12.5 A
(3)
Load impedance <45 mΩ, see
Max
15.5 A
Load impedance <45 mΩ, see
Max
5 A
Average (R.M.S.) current, load impedance 50 mΩ, see
Min
28 A
Up to 12 ms, load impedance <45 mΩ, see
Typ
30.5 A
Up to 12 ms, load impedance <45 mΩ, see
Output capacitance
Typ
4400 μF
Included inside the power supply
(1)
Power Boost: This power/ current is continuously allowed up to an ambient temperature of 45 °C (113 °F). Above this temperature, do not use this power or current longer than a duty cycle
of 10% and/or not longer than 1 minute every 10 minutes.
(2) HiccupPLUS Mode: At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2 s. After this, the output is switched off for
approximately 18 s before a new start attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device operates
normally. See
(3) Discharge current of output capacitors is not included.
Figure 8 - Output Voltage vs. Output Current, Typ
Figure 9 - Dynamic Output Current Capability, Typ
Output Voltage
0
0
12.5
4
8
12
28V
16
20
24
20 A
7.5
2.5
5
10
15 17.5
Adjustment
Range
Output Current
Continuous
current
Factory
setting
Hiccup
PLUS
mode
Output Voltage
(dynamic behavior, < 12 ms)
0
0
4
8
12
28V
16
20
24
50 A
20
10
30
40
5
15
25
35
45
Adjustment
Range
Output Current
Output
Current
0
14 A
18 s
18 s
18 s
2 s
2 s
2 s
t
Short -circuit
Normal
operation
Normal
operation