Rockwell Automation Publication 1606-RM101A-EN-P - July 2020
Environment
Attributes
Values
Notes
Operational temperature
(1)
(1)
Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2 cm
(0.79 in.) below the unit.
-25…+70 °C (-13...+158 °F)
Reduce output power according to
.
Storage temperature
-40…+85 °C (-40…+185 °F)
For storage and transportation
Output derating
3.2 W/1 °C (3.2 W/1.8 °F)
From 45…60 °C (113…140 °F)
6 W/1 °C (6 W/1.8 °F)
From 60…70 °C (140…158 °F)
Humidity 5…95%
r.h.
According to IEC 60068-2-30. Do not energize while
condensation is present.
Vibration sinusoidal
(2)
(2) Tested in combination with DIN rails according to EN 60715 with a height of 15 mm (0.59 in.) and a thickness of 1.3 mm (0.05 in.)
and standard orientation.
2…17.8 Hz: ±1.6 mm (0.06 in.);
17.8…500 Hz: 2 g 2 hours / axis
According to IEC 60068-2-6
Shock
30 g 6 ms, 20 g 11 ms,
3 bumps / direction,
18 bumps in total
According to IEC 60068-2-27
Altitude
0…2000 m (0…6560 ft)
Without any restrictions
2000…6000 m (6560…19,685 ft)
Reduce output power or ambient temperature, see
.
Altitude derating
15 W/1000 m (15 W/ 3281 ft) or
5 °C/1000 m (9 °F/ 3281 ft)
Above 2000 m (6500 ft), see
Overvoltage category
III
According to IEC 62477-1 for altitudes up to 2000 m (6560 ft)
II
According to IEC 62477-1 for altitudes from 2000…6000 m
(6560…19685 ft)
Degree of pollution
2
According to IEC 62477-1, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for use in
paint shops.
Corrosive gases
ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noise
Some audible noise may be emitted from the power supply during no load, overload, or short
circuit.
Figure 22 - Output Current vs. Ambient Temperature
Figure 23 - Output Current vs. Altitude
Allowed Output Current at 24V
0
-25
0
20
40
70 °C
2 A
4 A
6 A
8 A
10 A
12 A
60
A
Ambient Temperature
A... 85 to 264V AC, continuous
B... short term
B
0
0
2000 m
4000 m
6000 m
2 A
4 A
6 A
8 A
10 A
12 A
Allowed Output Current at 24V
Altitude
B
C
A ... Tamb < 60 °C
B... Tamb < 50 °C
C... Tamb < 40 °C
D... Short term
A
D