Rockwell Automation Allen-Bradley 1606-XLB120E Скачать руководство пользователя страница 8

8

Rockwell Automation Publication 1606-RM055B-EN-P - February 2017

Basic Power Supply 5 A

Input

Attribute

1606-XLB120E

AC input

nom

100…120V/200…240V AC

Auto-select, suitable for TN-, TT- and IT mains networks

AC input range

min

90…132V AC/180…264V AC

continuous operation

min

264…300V AC

< 500 ms

Allowed voltage L or N to earth

max

300V AC

continuous, IEC 62103

Input frequency

nom

50…60 Hz

±6%

External input protection

See recommendations in 

External Input Protection on page 16

Attribute

AC 100V

AC 120V

AC 230V

Input current

typ

2.0 A

1.72 A

1.05 A

at 24V, 5 A, see 

Figure 3

Power factor

(1)

typ

0.66

0.64

0.54

at 24V, 5 A, see 

Figure 5

Crest factor

(2)

typ

2.7

2.8

3.4

at 24V, 5 A

Turn-on voltage

typ

78V AC

78V AC

157V AC

at 24V 0 A, steady-state value, see 

Figure 2

Shut-down voltage

typ

68V AC

68V AC

68V AC

at 24V 5 A, steady-state value, see 

Figure 2

Start-up delay

typ

400 ms

400 ms

100 ms

see 

Figure 4

Rise time

typ

30 ms

30 ms

30 ms

at 24V, 5 A const. current load, 0mF load capacitance, see 

Figure 4

typ

90 ms

90 ms

90 ms

at 24V, 5 A const. current load, 5mF load capacitance, see 

Figure 4

Turn-on overshoot

max

200 mV

200 mV

200 mV

see 

Figure 4

(1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

(2) The crest factor is the mathematical ratio of the peak value to the T ms value of the input current waveform.

Figure 2 - Input Voltage Range, typ

Figure 4 - Turn-on Behavior, Definitions

Figure 3 - Input Current vs. Output Load at 24V

Figure 5 - Power Factor vs. Output Load

 

 

 

Turn-on

90

Rated input ranges

V

IN

P

OUT

264

180

Shut

-down

132

Upper

range

Lower

range

300Vac

max.

500ms

 

 

Start-up

delay

Rise

Time

Ov

ersh

oot

- 5%

Output
Voltage

Input
Voltage

 

 

 

5A

0.5 1 1.5 2 2.5 3 3.5 4 4.5

0

0.3

0.6

0.9

1.2

1.5

1.8

2.2A

Input Current, typ.

b

c

a

Output Current

a) 100Vac
b) 120Vac
c) 230Vac

Power Factor, typ.

0.5 1 1.5 2 2.5 3 3.5 4 4.5 5A

0.45

0.50

0.55

0.60

0.65

0.70

Output Current

a) 100Vac
b) 120Vac

c) 230Vac

b

c

a

 

Содержание Allen-Bradley 1606-XLB120E

Страница 1: ...Basic Power Supply 5 A Catalog Number 1606 XLB120E Reference Manual OriginalInstructions...

Страница 2: ...formation circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Th...

Страница 3: ...ts 6 Lifetime Expectancy and Mean Time between Failure MTBF 13 Protection Features 6 Functional Diagram 13 Safety Features 7 EMC 14 Installation Notes 7 Application Notes 15 Terminals and Wiring 7 Spe...

Страница 4: ...50 Hz mains frequency AC 120V parameters are valid for 60 Hz mains frequency AC 230V A figure that is displayed with the AC or DC before the value represents a nominal voltagewithstandardtolerances i...

Страница 5: ...wide input voltage range which makes it suitable for global use The addition of a DC OK signal makes the power supply ideal for many industry applications such as process automation and many other cri...

Страница 6: ...OK Relay Contact push in terminals Attribute 1606 XLB120E Output protection Electronically protected against overload no load and short circuits Output overvoltage protection typ 31V DC max 34V DC Inc...

Страница 7: ...PELV IEC EN 60204 1 EN 50178 IEC 62103 IEC 60364 4 41 Class of protection I PE Protective Earth connection required Isolation resistance 100 MOhm Input to output 500V DC Touch current leakage current...

Страница 8: ...400 ms 400 ms 100 ms see Figure 4 Rise time typ 30 ms 30 ms 30 ms at 24V 5 A const current load 0mF load capacitance see Figure 4 typ 90 ms 90 ms 90 ms at 24V 5 A const current load 5mF load capacitan...

Страница 9: ...A peak 40 A peak 40 C 104 F ambient cold start typ 18 A peak 22 A peak 33 A peak Inrush energy typ 13 A peak 16 A peak 30 A peak 25 C 77 F ambient cold start max 0 4 A2 s 0 5 A2 s 1 5 A2 s 40 C 104 F...

Страница 10: ...low 55 C 122 F ambient temperature 4 3 A at 28V below 55 C 122 F ambient temperature 2 5 A at 24V at 70 C 158 F ambient temperature 2 1 A at 28V at 70 C 158 F ambient temperature Derate linearly 50 70...

Страница 11: ...4V 5 A typ 26 ms 51 ms 50 ms min 22 ms 43 ms 42 ms Figure 10 Hold up Time vs Input Voltage Figure 11 Shut down behavior definitions 0 25 50 125ms 85 120 155 190 230Vac Input Voltage Hold up Time 75 10...

Страница 12: ...ad for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time Figure 13 Efficiency...

Страница 13: ...ng hours service life and is determined by the lifetime expectancy of the built in electrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated accordingto thecapaci...

Страница 14: ...208V AC 166V AC 70 of 208V AC 146V AC 50 of 208V AC 104V AC 80 of 120V AC 96V AC 70 of 120V AC 84V AC 50 of 120V AC 60V AC 1000 ms 500 ms 200 ms 1000 ms 500 ms 200 ms Criterion A Criterion A Criterio...

Страница 15: ...ely manner This avoids voltage loss in adjacent circuits The extra current peak current is supplied by the power converter and the built in large sized output capacitors of the power supply The capaci...

Страница 16: ...supply in parallel to increase the output power Parallel Use for Redundancy Power supplies can be paralleled for redundancy to gain higher system availability Redundant systems require a certain amou...

Страница 17: ...battery which is applied to the output terminals Keep an installation clearance left right of 15 mm 0 59 in between two power supplies and avoid installing the power supplies on top of each other Pay...

Страница 18: ...temperature for the power supply The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure The power supply is placed in the middle of the box...

Страница 19: ...put ripple 100 mVpp 20 Hz to 20 MHz AC Input voltage AC 100 120V 200 240V 10 Auto Select Mains frequency 50 60 Hz 6 AC Input current 1 72 A 1 05 A at 120 230V AC Power factor 0 64 0 54 at 120 230V AC...

Страница 20: ...5W 1000m or 5 C 1000m 2000 m 6500 ft see Figure 23 Overvoltage category III IEC 62103 EN 50178 altitudes up to2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not condu...

Страница 21: ...Strength To meet the PELV requirements according to EN60204 1 6 4 1 we recommend that either the pole the pole or any other part of the output circuit be connected to the protective earth system This...

Страница 22: ...tive EN 60950 1 EN 61000 6 UL 508 Listed for use as Industrial Control Equipment U S A UL 508 and Canada C22 2 No 14 15 File E56639 UL 60950 1 Recognized for use as Information Technology Equipment U...

Страница 23: ...g 0 81 lb DIN Rail Use 35 mm DIN rails according to EN 60715or EN 50022 witha height of 7 5 or 15 mm Plastic Material of Housing Flame retardant Polycarbonate PC UL94 V0 Vicat softening temperature sp...

Страница 24: ...24 Rockwell Automation Publication 1606 RM055B EN P February 2017 Basic Power Supply 5 A Notes...

Страница 25: ......

Страница 26: ...al Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer http www rockwellautomation com global support direct dial page Literature...

Отзывы: