Basic Power Supply 5 A

EMC

EMC Immunity

According to Generic Standards EN 61000-6-1 and EN 61000-6-2

Criterion

(1)

Electrostatic discharge

EN 61000-4-2

contact discharge 
air discharge

8 kV 
8 kV

Criterion A 
Criterion A

Electromagnetic RF field

EN 61000-4-3

80 MHz-2.7 GHz

20V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

input lines 
output lines 
DC-OK signal 

 

(coupling clamp)

4 kV 
2 kV 
2 kV

Criterion A 
Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5

L ->N 
L ->PE, N ->PE

2 kV 
4 kV

Criterion A 
Criterion A

Surge voltage on output

EN 61000-4-5

+ ->- 
+/- ->PE

500V 
1 kV

Criterion A 
Criterion A

Surge voltage on DC-OK

EN 61000-4-5

DC-OK signal… PE

1 kV

Criterion A

Conducted disturbance

EN 61000-4-6

0.15…80 M Hz

20V

Criterion A

Mains voltage dips

EN 61000-4-11

0% of 100V AC 
40% of 100V AC
70% of 100V AC 
0% of 200V AC
40% of 200V AC 
70% of 200V AC

0V AC, 20 ms
40V AC, 200 ms
70V AC, 500 ms
0V AC, 20 ms
80V AC, 200 ms
140V AC, 500 ms

Criterion A 
Criterion C 
Criterion A

(2)

Criterion A 
Criterion C
Criterion A

Voltage interruptions

EN 61000-4-11

0% of 220V AC (=0V)

5000 ms

Criterion C

Voltage sags

SEMI F47 0706

dips on the input voltage according to SEMI F47 standard

80% of 208V AC (166V AC) 
70% of 208V AC (146V AC) 
50% of 208V AC (104V AC) 
80% of 120V AC (96V AC)
70% of 120V AC (84V AC) 
50% of 120V AC (60V AC)

1000 ms 
500 ms 
200 ms 
1000 ms 
500 ms 
200 ms

Criterion A 
Criterion A 
Criterion C 
Criterion A 
Criterion A 
Criterion C

Powerful transients

VDE 0160

over entire load range

750V, 1.3 ms

Criterion A

(1) Criterion A: Power supply shows normal operation behavior withing the defined limits. 

 

Criterion C: Temporary loss of function is possible. Power supply can shut down and restart by itself. No damage or hazard for the 
power supply occurs.

(2) Below 4.5 A, Criterion C for currents above 5 A.

EMC Emission

According to Generic Standards: EN 61000-6-3, EN 610000-6-4

Conducted emission input lines

EN 55011, EN 55022
FCC Part 15
CISPR 11, CISPR 22

Class B

Conducted emission output 
lines

(1)

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

limits for DC power port according to EN 
61000-6-3 not fulfilled

Radiated emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

Fulfilled for class A equipment

Voltage fluctuations, flicker

EN 61000-3-3

Fulfilled

(2)

This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device cannot 
cause harmful interference, and (2) this device must accept any interference received, including interference that can 
cause undesired operation.

(1) For information only, not mandatory for EN 61000-6-3.

(2) Tested with constant current loads, non-pulsing.

Содержание Allen-Bradley 1606-XLB120E

Страница 1: ...Basic Power Supply 5 A Catalog Number 1606 XLB120E Reference Manual OriginalInstructions...

Страница 2: ...formation circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Th...

Страница 3: ...ts 6 Lifetime Expectancy and Mean Time between Failure MTBF 13 Protection Features 6 Functional Diagram 13 Safety Features 7 EMC 14 Installation Notes 7 Application Notes 15 Terminals and Wiring 7 Spe...

Страница 4: ...50 Hz mains frequency AC 120V parameters are valid for 60 Hz mains frequency AC 230V A figure that is displayed with the AC or DC before the value represents a nominal voltagewithstandardtolerances i...

Страница 5: ...wide input voltage range which makes it suitable for global use The addition of a DC OK signal makes the power supply ideal for many industry applications such as process automation and many other cri...

Страница 6: ...OK Relay Contact push in terminals Attribute 1606 XLB120E Output protection Electronically protected against overload no load and short circuits Output overvoltage protection typ 31V DC max 34V DC Inc...

Страница 7: ...PELV IEC EN 60204 1 EN 50178 IEC 62103 IEC 60364 4 41 Class of protection I PE Protective Earth connection required Isolation resistance 100 MOhm Input to output 500V DC Touch current leakage current...

Страница 8: ...400 ms 400 ms 100 ms see Figure 4 Rise time typ 30 ms 30 ms 30 ms at 24V 5 A const current load 0mF load capacitance see Figure 4 typ 90 ms 90 ms 90 ms at 24V 5 A const current load 5mF load capacitan...

Страница 9: ...A peak 40 A peak 40 C 104 F ambient cold start typ 18 A peak 22 A peak 33 A peak Inrush energy typ 13 A peak 16 A peak 30 A peak 25 C 77 F ambient cold start max 0 4 A2 s 0 5 A2 s 1 5 A2 s 40 C 104 F...

Страница 10: ...low 55 C 122 F ambient temperature 4 3 A at 28V below 55 C 122 F ambient temperature 2 5 A at 24V at 70 C 158 F ambient temperature 2 1 A at 28V at 70 C 158 F ambient temperature Derate linearly 50 70...

Страница 11: ...4V 5 A typ 26 ms 51 ms 50 ms min 22 ms 43 ms 42 ms Figure 10 Hold up Time vs Input Voltage Figure 11 Shut down behavior definitions 0 25 50 125ms 85 120 155 190 230Vac Input Voltage Hold up Time 75 10...

Страница 12: ...ad for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time Figure 13 Efficiency...

Страница 13: ...ng hours service life and is determined by the lifetime expectancy of the built in electrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated accordingto thecapaci...

Страница 14: ...208V AC 166V AC 70 of 208V AC 146V AC 50 of 208V AC 104V AC 80 of 120V AC 96V AC 70 of 120V AC 84V AC 50 of 120V AC 60V AC 1000 ms 500 ms 200 ms 1000 ms 500 ms 200 ms Criterion A Criterion A Criterio...

Страница 15: ...ely manner This avoids voltage loss in adjacent circuits The extra current peak current is supplied by the power converter and the built in large sized output capacitors of the power supply The capaci...

Страница 16: ...supply in parallel to increase the output power Parallel Use for Redundancy Power supplies can be paralleled for redundancy to gain higher system availability Redundant systems require a certain amou...

Страница 17: ...battery which is applied to the output terminals Keep an installation clearance left right of 15 mm 0 59 in between two power supplies and avoid installing the power supplies on top of each other Pay...

Страница 18: ...temperature for the power supply The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure The power supply is placed in the middle of the box...

Страница 19: ...put ripple 100 mVpp 20 Hz to 20 MHz AC Input voltage AC 100 120V 200 240V 10 Auto Select Mains frequency 50 60 Hz 6 AC Input current 1 72 A 1 05 A at 120 230V AC Power factor 0 64 0 54 at 120 230V AC...

Страница 20: ...5W 1000m or 5 C 1000m 2000 m 6500 ft see Figure 23 Overvoltage category III IEC 62103 EN 50178 altitudes up to2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not condu...

Страница 21: ...Strength To meet the PELV requirements according to EN60204 1 6 4 1 we recommend that either the pole the pole or any other part of the output circuit be connected to the protective earth system This...

Страница 22: ...tive EN 60950 1 EN 61000 6 UL 508 Listed for use as Industrial Control Equipment U S A UL 508 and Canada C22 2 No 14 15 File E56639 UL 60950 1 Recognized for use as Information Technology Equipment U...

Страница 23: ...g 0 81 lb DIN Rail Use 35 mm DIN rails according to EN 60715or EN 50022 witha height of 7 5 or 15 mm Plastic Material of Housing Flame retardant Polycarbonate PC UL94 V0 Vicat softening temperature sp...

Страница 24: ...24 Rockwell Automation Publication 1606 RM055B EN P February 2017 Basic Power Supply 5 A Notes...

Страница 25: ......

Страница 26: ...al Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer http www rockwellautomation com global support direct dial page Literature...

Отзывы: