Chapter
2
Installation and Wiring
Storage and Operation Conditions
Follow these recommendations to prolong drive life and performance:
• Store within an ambient temperature range of –40
°
to +85
°
C.
• Store within a relative humidity range of 0% to 95%, non-condensing.
• Protect the cooling fan by avoiding dust or metallic particles.
• Avoid storing or operating the drive where it could be exposed to a corrosive
atmosphere.
• Protect from moisture and direct sunlight.
• Operate at an ambient temperature range of 0
°
to +50
°
C.
CE Compliance
Refer to Appendix C.
Installation
Mount the drive on a flat, vertical and level surface. See Chapter 1, Figure 1.3 for
mounting orientation.
Choose an installation method:
• Install with screws. Recommended screw size is listed in the table below.
The appropriate drilling template for your drive is provided in Appendix B.
• Install on 35 mm DIN Rail. This mounting method is not available on
4.0 kW (5 HP) three phase or 1.5 kW (2 HP) single phase models.
See Appendix B for details on drive dimensions and weights.
Clearances
Maintain 12.5 mm (0.5 in.) clearance at the top, bottom, and front of all drives.
Clearance requirements between units varies by model.
• 2.2 kW (3 HP) 230V/460V Drives
Provide a minimum of 8.5 mm (0.33 in.) clearance between units.
• All Other Drive Ratings
No clearance is required between units.
Debris Label
The drive is shipped with a paper debris label attached to the top side of the plastic
housing to cover the cooling vents. Leave the debris label attached during drive
installation to protect against debris falling through the vents of the drive housing.
To assure proper drive operation, you must remove label before applying power.
Description
Metric
English
Minimum Panel Thickness (14 GA)
1.9 mm
0.0747 in.
Mounting Base Screws
m4 x 0.7
# 8-32
Mounting Torque
1.13 – 1.56 Nm
10 – 14 lb.-in.
ATTENTION:
After system installation, remove the debris label
from unit. Failure to remove this label may result in overheating or
nuisance tripping.
Содержание Allen-Bradley 160 SSC Series
Страница 12: ...1 6 Getting Started End of Chapter ...
Страница 58: ...5 20 Parameters and Programming End of Chapter ...
Страница 66: ...A 4 Specifications End of Chapter ...
Страница 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Страница 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Страница 82: ...C 6 CE Conformity End of Chapter ...
Страница 87: ......