Rockwell Automation Publication 150-UM009E-EN-P - August 2021
26
Chapter
5
Specifications
Electrical
Table 21 - Power Circuit
UL/cUL/CSA
IEC
Rated Operational Voltage
200…600V AC
200…500V AC
Rated Insulation Voltage
600V AC
500V AC
Di-electric Withstand
2200V AC
2500V AC
Repetitive Peak
200…600V AC: 1600
500V AC: 1600
Rated Impulse Voltage
6 kV
Overvoltage Category
III
Number of Poles
Equipment designed for 3-phase only
Operating Frequency
50/60 Hz
Controller Utilization Category
32/52/64
AC-53b: 3.5-15:3585
74/104/147
AC-53b: 4.5-30:1770
234
AC-53b: 3.5-30:1770
Line
Delta
Overload Current Range [A]
32
6.3…19
10.9…32.9
51
10…30
17…51
64
12.3…37
21.3…64
74
14.3…43
24.7…74
104
20…60
34.7…104
147
28.3…85
49…147
234
34…135
59…234
Table 22 - Control Circuit
UL/cUL/CSA
IEC
Rated Operational Voltage
100…120V AC, 200…240V AC
120V AC, 240V AC
Rated Insulation Voltage
—
300V AC
Di-electric Withstand
—
3000V
Rated Impulse Voltage
3 kV
Operating Frequency
50/60 Hz
Control Power Requirements
32/52/64
215 mA @ 120V AC
180 mA @ 240V AC
74/104/147
200 mA @ 120V AC
100 mA @ 240V AC
234
200 mA @ 120V AC
120 mA @ 240V AC
Fan Power Requirements
32/52/64
—
74/104/147
—
234
20VA