Installation
Transport System Installation
186
MagneMotion
Rockwell Automation Publication MMI-UM007F-EN-P - September 2020
Mounting the 2198-Pxxx DC-bus Power Supplies
Install the 2198-Pxxx DC-bus power supplies inside the approved metal enclosure (IP54 min)
where the inverters are installed. Run input power wiring in conduit (grounded to the enclo-
sure) outside of the enclosure. Separate signal and power cables. The 2198-Pxxx DC-bus
power supplies and QSHT 5700 inverters must be spaced in the enclosure by aligning the
zero-stack tab and cutout as shown in
. For hole patterns, see the
Kinetix 5700 Servo
Drives User Manual
.
QSHT 5700 Drive System Power Supply Ground Screw/Jumper Settings
Determine the ground screw/jumper setting for the 2198-Pxxx DC-bus power supply and
QSHT 5700 inverters. The 2198-Pxxx DC-bus power supplies have a factory-installed ground
screw for grounded-wye power distribution.
details the ground screw/jumper set-
tings for the 2198-Pxxx DC-bus power supply.
To access the ground screw on the 2198-Pxxx DC-bus power supplies, open the small plastic
door on the right side of the module as shown in
. It is recommended that the
ground screw be installed with the power supply removed from the panel and placed on its
side on a solid surface equipped as a grounded static-safe workstation.
Table 5-2: Ground Screw/Jumper Setting for the DC-bus Power Supply
Ground Configuration
2198-Pxxx DC-bus Power Supply
Grounded (wye)
Ground screw installed (default setting)
*
*
Ground screw is factory installed.
•
Impedance grounded
•
Corner grounded
•
AC-fed ungrounded
Remove ground screw/jumper
IMPORTANT
If the facility uses a grounded-wye power distribution, do not
remove the ground screw from the DC-bus power supply.
Remove the ground screw when using ungrounded, cor-
ner-grounded, or impedance-grounded power.
IMPORTANT
If grounded-wye power distribution is being used with a
2198-Pxxx DC-bus power supply, install the ground screw.
For grounded-wye power distribution, EMC performance
can be affected if the ground screw is not installed.