Wiring the Regulator Board and RMI Board Terminal Strips
7-17
Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring the Reset Input
22
Digital Input 3
(Reset)
The following parameter must be set:
•
P.000: Control Source
Terminal 22 On = Reset
Wiring the Stop/Start Inputs
23
24
Digital Input 2
(Stop)
Digital Input 1
(Start)
The following parameter must be set:
•
P.000: Control Source
•
P.025: Stop Type
Terminal 23 Off = Stop
Terminal 24 On Transition = Start
25
24 VDC Isolated Common
Reserved Teminals
26
27
No Connection
+24 VDC Isolated Common
Terminal 26 has no connection and is not used in LiquiFlo
applications. Terminal 27 can be used as a 24V DC common.
Содержание 41LR4060
Страница 6: ...IV LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 8: ...VI LiquiFlo 2 0 AC Drive User Manual ...
Страница 10: ...VIII LiquiFlo 2 0 AC Drive User Manual ...
Страница 12: ...1 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 15: ...About the Drive 2 3 Figure 2 2 B Frame LiquiFlo Drive Component Locations 1 2 3 4 10 9a 8 7 6 5 12 9b 11 ...
Страница 19: ...About the Drive 2 7 Figure 2 4 D Frame LiquiFlo Drive Component Locations 8 9 7 6 5 4 3 2 1 13 10 11 12 14 ...
Страница 30: ...2 18 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 40: ...3 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 50: ...4 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 78: ...7 22 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 90: ...9 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 96: ...B 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Страница 98: ...C 2 LiquiFlo 2 0 AC Drive User Manual ...
Страница 100: ...D 2 LiquiFlo 2 0 AC Drive User Manual ...
Страница 102: ...E 2 LiquiFlo 1 5 AC Power Modules Hardware Reference Version 1 2 ...
Страница 107: ......