![Rockwell Automation 1606-XLS80E Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/rockwell-automation/1606-xls80e/1606-xls80e_instruction-manual_1475724004.webp)
1606-XLS80E Power Supply Instruction Manual
Safety
Separation of output
SELV
IEC/EN 60950-1
EMC
The device is suitable for applications in industrial environment as well as in residential,
commercial and light industry environment without any restrictions.
For further details see datasheet.
PELV
EN 60204-1, EN 50178, IEC 60364-4-41
EMC Immunity
EN 61000-6-1, EN 61000-6-2
Touch current
max. 0.3 mA
Earth leakages current, TN- mains
Isolation resistance
min. 5MOhm
Input to output, 500Vdc
EMC Emission
EN 61000-3-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-4,
FCC Part 15 Class B
PE resistance
max. 0.1Ohm
Between housing and ground terminal
Transformer
Safety transformer according to IEC/EN 61558-2-17
This device complies with FCC Part 15 rules. Operation is subjected to following two
conditions: (1) this device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
Approvals
See datasheet or markings on the unit
CE mark in conformance with EMC guideline 89/336/EEC and 93/68/EEC and low-voltage directive (LVD) 73/23/EWG.
Terminals and Connections
Terminals
Input
Output
Type
Bi-stable, quick-connect spring clamp terminals
Ferrules
Allowed, but not required
Solid wire
0.5-6mm
2
0.3-4mm
2
Stranded wire
0.5-4mm
2
0.3-2.5mm
2
AWG
AWG 20-10
AWG 28-12
Stripping length
10mm / 0.4inch
6mm / 0.25inch
Pull-out force
10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (UL486E)
1. Insert the wire
2. Snap the lever
Use appropriate copper cables that are designed for an operating temperatures of 60°C (for ambient
up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point (except PE wire). Do
not use without PE (Ground) connection!
Physical Dimensions, Indicators and Cooling
Width
32mm / 1.26’’
Height
124mm / 4.88’’
Depth
102mm / 4.02’’
Plus DIN-rail depth
Weight
420g / 0.93lb
DIN-Rail
Use DIN-rails according to EN 60715 or EN 50022
with a height of 7.5 or 15mm
Mounting
Orientation
Output terminal on top and input terminals on the bottom.
For other orientations consult factory.
Indicators
DC-ok LED
(green)
Overload
lamp (red)
Normal operating mode
ON
OFF
BonusPower
®
operation
ON
OFF
Overload (V
OUT
< 90%)
ON
ON
Overload (V
OUT
< 80%)
OFF
ON
Short-circuit (V
OUT
= 0)
OFF
ON
Temperature shut-down
Flashing
Flashing
No input power
OFF
OFF
Do not obstruct air flow!
The unit is convection cooled.
Ventilation grid must be kept free of any obstructions.
Keep installation clearances at higher ambient temperature and full load:
60mm on top and on the bottom, 15mm on the left and right side
PU-358.010.38-10A
Operation on Two Phases
240V max.
Fuse
DC
L
N
PE
N
L2
Center
Tap
L1
L3
(1) The rated supply voltage must be below
240V.
(2) Use an appropriate fuse to protect the N
terminal!
Parallel Operation
Power Supply A
Power Supply B
-
AC
DC
+
-
AC
DC
+
Load
+
-
Fuse
*)
Fuse
*)
(1) Power supplies can be paralleled to
increase output power or to build redundant
systems.
(2) For parallel operation use power supplies
of the same family.
(3) Use load connection wires of the same
gauge and length.
(4) Set the output voltages of all power
supplies to the same value.
(5) A fuse is only required if more than three
units are connected in parallel.
Serial Operation
Load
Power Supply A
Power Supply B
+
-
AC
DC
+
-
AC
DC
+
-
Earth
*)
(1) It is possible to connect as many units in
series as needed, providing the sum of the
voltage does not exceed 150Vdc.
(2) For serial operation use power supplies
of the same type.
(3) Grounding of the output is required when
the sum of the output voltage exceeds
60Vdc.
Operation with DC Input
Fuse
+
-
Load
+
-
DC
L
N
PE
AC
+
-
(1) The power supply will operate with a DC
input voltage.
(2) Use a battery or similar DC source.
(3) Cpole to L and –pole to N
(4) In case the –pole of the battery is not
grounded, use an appropriate fuse to protect
the N terminal.
(5) Connect the ground terminal of the power
supply to a PE wire or to machine ground.
Check touch current (earth leakage current)! The total touch current is the sum of
the touch currents of all units. Safety limits – depending on the field of application
- apply for the allowed touch current!
Air flow
open
close