background image

5

- A cable compliant with the corresponding low voltage standards 
must be used. Remember that the green and yellow earth wire 
must have a length at least 40 mm longer than the neutral cables 
so that in the case of the cables being pulled, it is the last to be 
disconnected.

- If the mains connection is made below the spa, it must be done by 
means of a connection system with a protection level of at least IPX5 
and it must be located at more than 20 cm from the floor.

It is very important to make sure that the electrical connections are 
completely watertight (IPX5 level).

5. HYDRAULIC CONNECTION

Filling the spa can be done directly by garden hose or by use inlet 
check valve (fig. 6).

For the connection, use PVC pipes and appropriate adhesive for this 
type of material. Do not use metal pipes.

Make sure that there are no accumulated bags of air or water in 
the fill or empty connection. The emptying circuit must guarantee 
perfect emptying and, if the use of the drain so allows, a U-bend to 
prevent bad smells.

Also, where required, the fill and empty circuits must also be fitted 
with anti-backflow devices to prevent retrosuction..

Once the installation is complete, start up the equipment and check 
that the joints are watertight. Mark the water level in the spa, leave it 
for 24 hours and check that it has not gone down.

The following drawing (fig. 7), shows the spa’s filter circuit.

2,4

m

2,4

m

Vol. 1

Vol. 1

Vol. 0

Vol. 3

V

o

l.

2

V

o

l.

2

2,25 m

0,6 m

0,6 m

0,2 m

Vol. 3

Please note: The space below the spa tank is considered volume 3

as a tool is required to remove the panels.

2,4

m

2,4

m

Vol. 1

Vol. 1

Vol. 0

Vol. 3

V

o

l.

2

V

o

l.

2

2,25 m

0,6 m

0,6 m

0,2 m

Vol. 3

Please note: The space below the spa tank is considered volume 3

as a tool is required to remove the panels.

6. FILLING AND EMPTYING THE SPA

Never use the air blower circuit to fill the spa.

The spa can be connected to the water mains pipes, permanently 
in use, or it can be filed and emptied by flexible pipes that can be 
removed after use.

Figure 8 shows the filling point of the spa with the letter I.

Figure 8 shows the emptying point of the spa with the letter V, which 
can be permanently or temporarily connected to the conduit system. 
Said emptying outlet must be connected to the general drain in the 
room or house. We recommend the use of a U-bend to avoid bad 
smells. The empty/fill taps are marked with the letter T.

For your convenience, for both the filling and emptying operations, 
we recommend the installation of taps outside the spa enclosure. 
This will avoid the need for removing the panels.

7. VENTILATION

The possible high temperature of the water in the spa (approximately 
39 ºC) leads to steam condensation.

The spa room must have adequate ventilation. If it does not, it is re-
commended that you install a dehumidifier to keep the air humidity 
at a constant temperature and prevent steam from condensing on 
the ceiling and on the floor.

For the correct maintenance of the wood, the relative air humidity 
in the room must be kept below 65% when the spa is not being 
used. 

During use and due to the evaporation caused by the hydromas-
sage and the movement of the water, this value normally reaches 
90 or 95%.

The air humidity can be kept constant by the use of fans controlled 
by hygrostats or dehumidifiers adapted to the size of the room. Your 
installer or distributor can offer you advice on this. If the room has air 
conditioning, the condenser is not necessary. If the spa is outdoors 
or in an open space, these apparatuses are not necessary.

Fig. 5

Fig. 6

Содержание Broadway Round

Страница 1: ...1 Installation Instructions SPA BROADWAY ROUND...

Страница 2: ...PREPARING THE PLACE FOR THE INSTALLATION 4 3 POSITIONING THE SPA 4 4 ELECTRICAL CONNECTIONS 4 4 1 Earth connection 4 4 2 Equipotential connection 4 4 3 Mains situation 4 4 4 Mains connection 4 5 HYDRA...

Страница 3: ...cally the blower pump Between 15 and 12 blower operates for 1 minute every 120 minutes Between 12 and 9 blower operates for 1 minute every 60 minutes Between 9 and 6 blower operates for 1 minute every...

Страница 4: ...r next to a side wall remember toleave0 5metresorconnectionorinstallationworkorfittrapdoors with a minimum size of 1700x700 mm for accessing all the sides for post installation maintenance This spa ca...

Страница 5: ...Vol 3 Please note The space below the spa tank is considered volume 3 as a tool is required to remove the panels 6 FILLING AND EMPTYING THE SPA Never use the air blower circuit to fill the spa The spa...

Страница 6: ...the Broadway Round D D P E H G F K R V T Z2 Z1 I D 2 air regulators P Control panel E Blower R Heating element F Filter skimmer T Empty fill tap G Ozone generator V Empty fill H Filter hydromassage p...

Страница 7: ...ER OZONE L1 N PE R91 R90 R89 R88 R120 R119 R118 R94 N L L N PE L N PE PUMP 1 PUMP 2 L LO N PE PUMP 2 L HI N PE PUMP 1 L LO N PE L HI N PE L1 L2 L3 N PE INPUT VOLTAGE LIGHT RELAY 30A 250VAC RELAY 16A 2...

Страница 8: ...ch km 2 5 B P 571 26000 Settat Maroc Telf 212 0 23 40 59 41 212 0 23 40 03 39 Fax 212 0 23 40 59 42 Roca GmbH Feincheswiese 17 56424 Staudt Deutschland Tel 49 0 2602 93610 Fax 49 0 2602 936 122 Roca P...

Отзывы: