background image

R8MUST-01

INSTRUCTION MANUAL

The emergency lighting must be inspected and tested 

regularly in accordance with local codes of practice: 

note: for safety reasons tests should be carried out 

during daylight hours.

The minimum recommended test schedule is as follows:

After installation, allow 24 hours to ensure full battery 

charge and then interrupt the supply; the maximum 

duration time is 3 hours check that LEDs are still 

lighting. 

1. Daily check that charge indicator LED is working

2. Monthly, interrupt mains for a short period and   

    check LED lights

3. Annual 12 month check, full duration test. 

    Interrupt mains supply, LEDs will light and 

    should last for a minimum 3 hours operation: 

    batteries must be replaced when they can no 

    longer support 3 hour operation.

4. Complete record sheet on installation and retain in 

    maintenance file.

5. Update file with ongoing test records for inspection 

    by fire officer or other duly authorised person

Testing

De noodverlichting moet regelmatig worden gecontroleerd en 
getest in overeenstemming met de plaatselijke praktijkrichtlijnen. 
Opmerking: om veiligheidsredenen moeten testen tijdens 
daglichturen worden uitgevoerd. Het minimum aanbevolen 
testschema ziet er als volgt uit:
Na installatie 24 uur wachten om ervoor te zorgen dat de batterij 
volledig is opgeladen en daarna de stroomvoorziening 
onderbreken; de maximum duur is 3 uur. Controleer of de leds 
nog licht geven. 

1. Controleer dagelijks of de ladingindicator van de led werkt.
2. Schakel maandelijks de stroomvoorziening even uit en 
controleer de ledlampen.
3. Verricht jaarlijks een complete inspectie, een test van volledige 
duur. Schakel de stroomvoorziening uit. De leds zullen oplichten 
en dienen ten minste 3 uur mee te gaan. De batterijen moeten 
worden vervangen als ze geen 3 uur meer werken.
4. Vul het registratieblad van de installatie in en bewaar in het 
onderhoudsbestand.
5. Werk het bestand bij met de verschillende testresultaten ter 
inspectie van de brandweer of een andere naar behoren 
bevoegde persoon.

Testen

UNIVERSAL EMERGENCY 

FITTING SELF TEST, WHITE

R8MUST-01

ZELFTEST VAN UNIVERSELE

NOODVERLICHTING, WIT

PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.

! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product, 

consult a competent electrician

                                                                                                           Note:

Product technical information and specification may change over time without prior notification. For the latest technical 

information please visit our web site www.ledgrouprobus.com or robusdirect.com

Issue 2 080914

Page 1

Information for the Product user:

Installation

1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste 

    (WEEE marked with crossed out wheelie bin symbol). 

2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre 

    for waste electrical equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.

3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly.  It is 

    important that it is separated from normal household waste and recycled in the WEEE chain

4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household 

    waste, but should be disposed of according to local WEEE regulations

The Installation must be carried out by a qualified electrician

1. Ensure mains supply is switched off before commencing work.

2. Press the latch on the two sides of unit, and then slide the 

    diffuser off

3. Remove 2 screws and pull the gear tray away from the fitting.

4. Mark appropriate fixing position on the ceiling or wall, Before 

    drilling establish the direction of buried cables and other 

    building services.

5 Surface mounting: Drill holes at the appropriate distance.

   Recessed mounting: Cut-out the required area to recess the 

   fitting into the wall or ceiling. Remove the two recess covers 

   from the sides.

6. Introduce supply cables into the base.

7. Fix fitting base to the ceiling or wall, ensure it is secure.

8. Connect wires from un-switched supply to terminals:

    Brown/Live to PL, Blue/ Neutral to N and Green/ Yellow to

    earth. For fitting always on, link terminal “SL” to terminal

    “PL”. When controlled by switch connect switched live wire

    to terminal SL and permanent live to PL. Note: if “SL”

    terminal not connected, fitting works as non-maintained

9. Refit the plate to base and ensure that it fits securely.

10. Attach diffuser to base.

R8MUST non-maintained procedure: 

11. In order for the R8MUST to operate correctly in 

      non-maintained operation the batteries must be fully depleted  

      until the Yellow is on continuously. Once the Yellow LED is 

      on flast flash the manual test button must be pressed and 

      held for over 3 seconds. When button is released the Yellow 

      LEDs will turn off. This process must be repeated for all

Note: In order to reset the fitting after lamp failure the manual test 

button must be pressed and held for 3 seconds.

1. Zorg dat het lichtnet is uitgeschakeld voordat u begint te werken.
2. Druk op de vergrendeling aan beide zijden van de eenheid en schuif 
    dan de lichtverspreider eraf
3. Verwijder 2 schroeven en trek de mechanismeplaat weg van het 
    armatuur.
4. Markeer de bevestigingspositie op het plafond of de muur, ga na of er 
    verborgen kabels en andere voorzieningen van het gebouw lopen 
    voordat u begint te boren.
5 Oppervlaktemontage: Boor de gaten op de uitgemeten afstand.
   Verzonken montage: Maak de nodige ruimte open om de verlichting in 
   de muur of het plafond te bevestigen. Verwijder de twee    
   verzinkingsplaten van de zijkanten.
6. Steek de stroomkabels in de onderplaat.
7. Bevestig de onderplaat van het armatuur tegen het plafond of de 
    muur, zorg dat deze goed vast zit.
8. Sluit de draden van de uitgeschakelde stroomvoorziening aan op de 
    aansluitklemmen: Bruin/Stroom op PL, Blauw/Neutraal op N en 
    Groen/Geel op aarding. Verbind om de verlichting permanent aan te 
    hebben de aansluitklem "SL" met de aansluitklem "PL". Verbind voor   
    bediening met schakelaar de geschakelde stroomdraad met 
    aansluitklem SL en permanente stroom met PL. Opmerking: als de 
    aansluitklem “SL” niet aangesloten is, werkt de verlichting als 
    niet-zelfstandig
9. Plaats de plaat terug op de onderplaaten zorg dat deze goed vast zit.
10. Bevestig de lichtverspreider op de onderplaat.
R8MUST niet-zelfstandige procedure:
11. Om de R8MUST juist in niet-zelfstandig bedrijf te laten werken 
     moeten de batterijen helemaal leeg zijn tot het Gele controlelampje 
     ononderbroken gaat branden. Wanneer de Gele LED snel knippert,   
     moet u op de knop handmatige test drukken en minstens 3 seconden 
     ingedrukt houden. Wanneer u de knop loslaat, gaan de Gele
     LEDs uit. Dit proces moet voor alle eenheden worden herhaald
Opmerking: Om de verlichting te resetten na een storing van de lamp, 
moet u de knop 3 seconde ingedrukt houden voor een handmatige test.

5°C < Ta < +25°C, 220V – 240V ~ 50/60Hz, Class I, IP20

Lamp type: T5 8W fluorescent tube

5°C < Ta < +25°C, 220V – 240V ~ 50/60Hz, 

Klasse I

, IP20

Lamptype: T5 8W fluorescentiebuis

Installatie

LEES DE INSTRUCTIES VOORDAT U BEGINT MET DE INSTALLATIE EN HOU ZE BIJ VOOR LATER.

! Elektrische producten kunnen de dood of letsel veroorzaken of eigendommen beschadigen. Als u twijfelt over de installatie of 

het gebruik van dit product, raadpleeg dan een erkende elektricien

                                                                                                    Opmerkingen: 

Technische gegevens en specificaties van dit product kunnen zonder voorafgaande kennisgeving wijzigen. Ga voor de meest 

recente technische gegevens naar onze website www.ledgrouprobus.com of robusdirect.com

Informatie voor de gebruiker van het product:

1. Hou bij het verwijderen van afval rekening met de regeling voor afgedankte elektrische en elektronische apparatuur, gescheiden van 

    gewoon huishoudelijk afval (AEEA, pictogram van een kliko met een kruis erdoorheen).

2. Neem uw verantwoordelijkheid op het vlak van hergebruik en recycling door dit product aan het einde van zijn levenscyclus in te 

    leveren bij een inleverpunt voor elektronisch afval, een milieupark of een winkel waar u een nieuw product koopt.

3. Deze apparatuur kan stoffen bevatten die gevaarlijk zijn voor de gezondheid en het milieu indien ze onachtzaam wordt weggegooid. 

    Het is belangrijk dat ze gescheiden gehouden wordt van het normaal huishoudelijk afval en gerecycled wordt in het netwerk voor 

    AEEA.

4. Het pictogram van een kliko met een kruis erdoorheen op een product betekent dat dit apparaat niet samen met het gewone 

    huishoudelijk afval mag worden weggegooid, maar dat het dient te worden verwijderd in overeenstemming met de lokale regelgeving 

    voor AEEA (afgedankte elektrische en elektronische apparatuur).

De installatie dient te worden uitgevoerd door een elektricien

EN

NL

LED FUNCTIONS GUIDE

Green

Yellow

*Fast flash

*Slow flash

Red

Status

Normally charging mode

Battery insufficient capacity

Lamp replacement required or 
lamp not inserted incorrectly

Self-test or manual test

Normally emergency 
     discharging

BESCHRIJVING LEDFUNCTIES

Groen

Geel

*Snel 
knipperen

*Langzaam 
knipperen

Rood

Status

Normaal laden

Batterij bijna leeg

Lamp moet worden vervangen 
of lamp niet correct geplaatst

Zelftest of handmatige test

Normale noodontlading

Отзывы: