The emergency lighting must be inspected and tested
regularly in accordance with local codes of practice:
note: for safety reasons tests should be carried out
during daylight hours.
The minimum recommended test schedule is as follows:
After installation, allow 24 hours to ensure full battery
charge and then interrupt the supply; the maximum
duration time is 3 hours check that LEDs are still
lighting.
1. Daily check that charge indicator LED is working
2. Monthly, interrupt mains for a short period and
check LED lights
3. Annual 12 month check, full duration test.
Interrupt mains supply, LEDs will light and
should last for a minimum 3 hours operation:
batteries must be replaced when they can no
longer support 3 hour operation.
4. Complete record sheet on installation and retain in
maintenance file.
5. Update file with ongoing test records for inspection
by fire officer or other duly authorised person
Testing
De noodverlichting moet regelmatig worden gecontroleerd en
getest in overeenstemming met de plaatselijke praktijkrichtlijnen.
Opmerking: om veiligheidsredenen moeten testen tijdens
daglichturen worden uitgevoerd. Het minimum aanbevolen
testschema ziet er als volgt uit:
Na installatie 24 uur wachten om ervoor te zorgen dat de batterij
volledig is opgeladen en daarna de stroomvoorziening
onderbreken; de maximum duur is 3 uur. Controleer of de leds
nog licht geven.
1. Controleer dagelijks of de ladingindicator van de led werkt.
2. Schakel maandelijks de stroomvoorziening even uit en
controleer de ledlampen.
3. Verricht jaarlijks een complete inspectie, een test van volledige
duur. Schakel de stroomvoorziening uit. De leds zullen oplichten
en dienen ten minste 3 uur mee te gaan. De batterijen moeten
worden vervangen als ze geen 3 uur meer werken.
4. Vul het registratieblad van de installatie in en bewaar in het
onderhoudsbestand.
5. Werk het bestand bij met de verschillende testresultaten ter
inspectie van de brandweer of een andere naar behoren
bevoegde persoon.
Testen
UNIVERSAL EMERGENCY
FITTING SELF TEST, WHITE
R8MUST-01
ZELFTEST VAN UNIVERSELE
NOODVERLICHTING, WIT
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product,
consult a competent electrician
Note:
Product technical information and specification may change over time without prior notification. For the latest technical
information please visit our web site www.ledgrouprobus.com or robusdirect.com
Issue 2 080914
Page 1
Information for the Product user:
Installation
1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste
(WEEE marked with crossed out wheelie bin symbol).
2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre
for waste electrical equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.
3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly. It is
important that it is separated from normal household waste and recycled in the WEEE chain
4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household
waste, but should be disposed of according to local WEEE regulations
The Installation must be carried out by a qualified electrician
1. Ensure mains supply is switched off before commencing work.
2. Press the latch on the two sides of unit, and then slide the
diffuser off
3. Remove 2 screws and pull the gear tray away from the fitting.
4. Mark appropriate fixing position on the ceiling or wall, Before
drilling establish the direction of buried cables and other
building services.
5 Surface mounting: Drill holes at the appropriate distance.
Recessed mounting: Cut-out the required area to recess the
fitting into the wall or ceiling. Remove the two recess covers
from the sides.
6. Introduce supply cables into the base.
7. Fix fitting base to the ceiling or wall, ensure it is secure.
8. Connect wires from un-switched supply to terminals:
Brown/Live to PL, Blue/ Neutral to N and Green/ Yellow to
earth. For fitting always on, link terminal “SL” to terminal
“PL”. When controlled by switch connect switched live wire
to terminal SL and permanent live to PL. Note: if “SL”
terminal not connected, fitting works as non-maintained
9. Refit the plate to base and ensure that it fits securely.
10. Attach diffuser to base.
R8MUST non-maintained procedure:
11. In order for the R8MUST to operate correctly in
non-maintained operation the batteries must be fully depleted
until the Yellow is on continuously. Once the Yellow LED is
on flast flash the manual test button must be pressed and
held for over 3 seconds. When button is released the Yellow
LEDs will turn off. This process must be repeated for all
Note: In order to reset the fitting after lamp failure the manual test
button must be pressed and held for 3 seconds.
1. Zorg dat het lichtnet is uitgeschakeld voordat u begint te werken.
2. Druk op de vergrendeling aan beide zijden van de eenheid en schuif
dan de lichtverspreider eraf
3. Verwijder 2 schroeven en trek de mechanismeplaat weg van het
armatuur.
4. Markeer de bevestigingspositie op het plafond of de muur, ga na of er
verborgen kabels en andere voorzieningen van het gebouw lopen
voordat u begint te boren.
5 Oppervlaktemontage: Boor de gaten op de uitgemeten afstand.
Verzonken montage: Maak de nodige ruimte open om de verlichting in
de muur of het plafond te bevestigen. Verwijder de twee
verzinkingsplaten van de zijkanten.
6. Steek de stroomkabels in de onderplaat.
7. Bevestig de onderplaat van het armatuur tegen het plafond of de
muur, zorg dat deze goed vast zit.
8. Sluit de draden van de uitgeschakelde stroomvoorziening aan op de
aansluitklemmen: Bruin/Stroom op PL, Blauw/Neutraal op N en
Groen/Geel op aarding. Verbind om de verlichting permanent aan te
hebben de aansluitklem "SL" met de aansluitklem "PL". Verbind voor
bediening met schakelaar de geschakelde stroomdraad met
aansluitklem SL en permanente stroom met PL. Opmerking: als de
aansluitklem “SL” niet aangesloten is, werkt de verlichting als
niet-zelfstandig
9. Plaats de plaat terug op de onderplaaten zorg dat deze goed vast zit.
10. Bevestig de lichtverspreider op de onderplaat.
R8MUST niet-zelfstandige procedure:
11. Om de R8MUST juist in niet-zelfstandig bedrijf te laten werken
moeten de batterijen helemaal leeg zijn tot het Gele controlelampje
ononderbroken gaat branden. Wanneer de Gele LED snel knippert,
moet u op de knop handmatige test drukken en minstens 3 seconden
ingedrukt houden. Wanneer u de knop loslaat, gaan de Gele
LEDs uit. Dit proces moet voor alle eenheden worden herhaald
Opmerking: Om de verlichting te resetten na een storing van de lamp,
moet u de knop 3 seconde ingedrukt houden voor een handmatige test.
5°C < Ta < +25°C, 220V – 240V ~ 50/60Hz, Class I, IP20
Lamp type: T5 8W fluorescent tube
5°C < Ta < +25°C, 220V – 240V ~ 50/60Hz,
Klasse I
, IP20
Lamptype: T5 8W fluorescentiebuis
Installatie
LEES DE INSTRUCTIES VOORDAT U BEGINT MET DE INSTALLATIE EN HOU ZE BIJ VOOR LATER.
! Elektrische producten kunnen de dood of letsel veroorzaken of eigendommen beschadigen. Als u twijfelt over de installatie of
het gebruik van dit product, raadpleeg dan een erkende elektricien
Opmerkingen:
Technische gegevens en specificaties van dit product kunnen zonder voorafgaande kennisgeving wijzigen. Ga voor de meest
recente technische gegevens naar onze website www.ledgrouprobus.com of robusdirect.com
Informatie voor de gebruiker van het product:
1. Hou bij het verwijderen van afval rekening met de regeling voor afgedankte elektrische en elektronische apparatuur, gescheiden van
gewoon huishoudelijk afval (AEEA, pictogram van een kliko met een kruis erdoorheen).
2. Neem uw verantwoordelijkheid op het vlak van hergebruik en recycling door dit product aan het einde van zijn levenscyclus in te
leveren bij een inleverpunt voor elektronisch afval, een milieupark of een winkel waar u een nieuw product koopt.
3. Deze apparatuur kan stoffen bevatten die gevaarlijk zijn voor de gezondheid en het milieu indien ze onachtzaam wordt weggegooid.
Het is belangrijk dat ze gescheiden gehouden wordt van het normaal huishoudelijk afval en gerecycled wordt in het netwerk voor
AEEA.
4. Het pictogram van een kliko met een kruis erdoorheen op een product betekent dat dit apparaat niet samen met het gewone
huishoudelijk afval mag worden weggegooid, maar dat het dient te worden verwijderd in overeenstemming met de lokale regelgeving
voor AEEA (afgedankte elektrische en elektronische apparatuur).
De installatie dient te worden uitgevoerd door een elektricien
EN
NL
LED FUNCTIONS GUIDE
Green
Yellow
*Fast flash
*Slow flash
●
●
Red
Status
Normally charging mode
Battery insufficient capacity
Lamp replacement required or
lamp not inserted incorrectly
Self-test or manual test
Normally emergency
discharging
●
BESCHRIJVING LEDFUNCTIES
Groen
Geel
*Snel
knipperen
*Langzaam
knipperen
●
●
Rood
Status
Normaal laden
Batterij bijna leeg
Lamp moet worden vervangen
of lamp niet correct geplaatst
Zelftest of handmatige test
Normale noodontlading
●