 FEATURES  AND  TECHNICAL  DATA

 

1.1 

 

 FEATURES

1.1.1 

   Operation

The Supercromo gas-fired convector is an independent 

heating appliance with sealed combustion chamber and 

forced draught.

It has been designed to be installed inside the room to be 

heated.

It is suitable for operation with natural gas (G20) and LPG 

(G30/G31) (gas-fired convector belonging to category 

II

2H3+

 according to EN 1266).

The combustion air intake and the exhaust of flue gases 

take place outside via two coaxial pipes and are ensured 

by the operation of a blower placed in the combustion cir-

cuit. Therefore, the gas-fired convector must be installed 

on an external perimetral wall or close to it, depending 

on the maximum extension of the pipes (see Paragraph 

3.4 

p. 12).

The operation principle of the Supercromo gas-fired con-

vector is based on a convective motion of room air that 

passes through the gas-fired convector from bottom to 

top, is heated and diffused into the room through the up-

per grille. The recirculation of the room air is facilitated by 

the presence of a fan placed in the lower part of the gas-

fired convector.

For this reason, do not place clothes, newspa-

pers or any other object that could obstruct the 

air outlet directly on the grille. Also make sure 

that curtains, backs of chairs or furniture are 

not placed at a distance of less than 30 cm from 

the gas-fired convector.

The operation of the gas-fired convector, very simple in 

itself, is made completely automatic by the thermostatic 

regulation and the programmable timer (standard in the 

3002 model, optional in the 3001 model): the user is only 

required to switch on the gas-fired convector beforehand, 

to choose the desired temperature (set on the regulation 

thermostat) and, for the 3002 model, the operating period 

(set on the programmable timer).

The sealed combustion chamber is the best guarantee of 

safety for the environment in which the gas-fired convec-

tor is installed: there is no possibility of the products of 

combustion leak, nor is the oxygen necessary for combus-

tion taken from the environment. The appliance, once in-

stalled in accordance with the installation standards, does 

not require any ventilation openings in the room.

A flame detection device using an ionisation probe in-

terrupts the gas supply in the event of an accidental 

shutdown.

1.1.2 

   Mechanical  components

 

Sealed combustion chamber.

 

High-efficiency tubular steel heat exchanger.

 

Centrifugal fan.

 

Ø 49/35 mm coaxial combustion air intake and flue 

gas exhaust pipes.

 

External windproof terminal in aluminium alloy (pat-

ented).

 

Casing in epoxy powder-coated sheet metal.

 

Support bracket for wall mounting.

1.1.3 

   Control and safety devices

 

Electronic management board providing the follow-

ing functions:

 

„

burner ignition

 

„

flame monitoring

 

„

blower management and control

 

„

fan control

 

„

heat exchanger temperature probe control

 

Manual reset limit thermostat.

 

Flue gas exhaust blower.

 

Gas solenoid valve.

 

Thermostat for setting the desired temperature.

 

Programmable timer (standard on 3002 model, op-

tional on 3001 model).

Содержание Supercromo

Страница 1: ...Installation use and maintenance manual Supercromo Fired by natural gas LPG Independent gas fired convectors with direct exchange to heat small and medium sized rooms...

Страница 2: ...ered trademarks contained within this publication are not affected With the aim of continuously improving the quality of its products Robur S p A reserves the right to modify the data and contents of...

Страница 3: ...p 9 2 3 Appliance positioning p 10 2 4 Minimum clearance distances p 10 3 Heating engineer p 10 3 1 Warnings p 10 3 2 Supplied material p 10 3 3 Fuel gas supply p 10 3 4 Combustion products exhaust p...

Страница 4: ...al local regulations in force and the manu facturer s instructions provisions Misuse The appliance must only be used for the purpos es for which it has been designed Any other use is deemed hazardous...

Страница 5: ...s paints etc near the appliance Comply with current regulations Aggressive substances in the air The air of the installation site must be free from ag gressive substances Switching the appliance off D...

Страница 6: ...on products exhaust Fire safety and prevention Any other applicable law standard and regulation III 3 EXCLUSIONS OF LIABILITY AND WARRANTY Any contractual or extra contractual liability of the manufac...

Страница 7: ...operation of the gas fired convector very simple in itself is made completely automatic by the thermostatic regulation and the programmable timer standard in the 3002 model optional in the 3001 model...

Страница 8: ...and 3 Serial con nection of the coils terminals 2 and 4 F A Noise filter L Line M1 Limit thermostat M2 Fan thermostat M4 Control unit M9 2 A fuse N Neutral P1 Reset button RP7 Ignition electrode RP8 D...

Страница 9: ...C33 C63 residual head Pa 25 maximum equivalent length of coaxial exhaust duct m 1 sound power Lw max dB A 47 5 sound pressure Lp at 5 metres max dB A 28 5 Dimensions width mm 478 height mm 577 depth m...

Страница 10: ...ommended distance from the gas fired convector to the floor is 13 cm Figure 1 1 p 8 and possibly not more than 35 cm as higher heights would result in uneven heat distribution in the heated room Keep...

Страница 11: ...ce pipe union Perform connection in compliance with applicable regulations 3 3 3 Gas pipes sizing The gas pipes must not cause excessive pressure drops and consequently insufficient gas pressure for t...

Страница 12: ...ar Figure 1 1 p 8 3 4 2 Installation types The flue gas exhaust combustion air intake of the Supercromo gas fired convectors can be realised in one of the following ways With coaxial pipes with outlet...

Страница 13: ...installed with separate pipes suitable pipes and components available as optional must be used At the design stage it must be verified that the sum of the pressure drop of all components used does no...

Страница 14: ...r intake and flue gas exhaust pipes Do not damage or discard the cardboard jig with the drilling template required for installing the gas fired convector 3 Fix the jig to the wall where the gas fired...

Страница 15: ...e complete with heating body by loosening the fixing screws see Figure 3 7 p 15 and disconnect the casing earth cable 10 Fit the end of the flue gas exhaust pipe 35 mm onto the gas fired convector out...

Страница 16: ...not to work on live components Earthing The appliance must be connected to an effective earthing system installed in compliance with reg ulations in force It is forbidden to use gas pipes as earthing...

Страница 17: ...y Appliance defects or faults caused during transport or installation Gas smell Non compliant mains gas pressure Non compliant flue gas exhaust All situations that may involve operation abnormali ties...

Страница 18: ...e regula tor B by fully tightening its screw and adjusting the second stage regulator if necessary 6 When the adjustment is complete switch off the appliance After the adjustment stop and start the ap...

Страница 19: ...Reassemble the plug B 8 Turn on the gas fired convector and check the gas tightness of plug B 9 Check the gas pressure at the burner as described in Paragraph 5 2 1 p 17 10 Remove the LPG adhesive lab...

Страница 20: ...iance and the blower stops lighting up red signal light C The reset must be carried out manually using reset button A 8 Once the appliance is switched on turn knob B on the thermostat clockwise to inc...

Страница 21: ...n of the fan ther mostat by running the cables under the bracket 7 Use cable 93 black of the cable kit to connect the pro grammable timer terminals 2 and 4 to each other 8 Remove the room thermostat d...

Страница 22: ...wanted switching on and or switching off Pressing the TIMER button the on off programs set will be displayed Figure 6 4 15 combination of days in a week 1 From Monday to Sunday 2 Monday 3 Tuesday 4 We...

Страница 23: ...of gas fired con vector is the cleaning of the outer casing which must al ways be carried out with the appliance cold and without the use of solvents and the periodic removal of any dust that may accu...

Страница 24: ...odes is broken or badly posi tioned replace it or reposition it For a correct ignition the distance between the two ignition electrodes must be about 3 5 mm D The detection electrode is broken or badl...

Страница 25: ...ons possible room temperature control with presence detec on room temperature control with open window detec on with distance control op on with adap ve start control with working me limita on with e...

Страница 26: ...h presence detec on room temperature control with open window detec on with distance control op on with adap ve start control with working me limita on with electronic room temperature control plus we...

Страница 27: ......

Страница 28: ...on of safe environmentally friendly energy efficiency products through the commitment and caring of its employees and partners Robur S p A advanced technologies for air conditioning via Parigi 4 6 240...

Отзывы: