Installation and operation manual – remote control
7
4
CONFIGURATION OF THE OPERATING PARAMETERS
This Paragraph is reserved exclusively for the author-
ised Robur Technical Assistance Centre.
Incorrect configuration of the remote control may cause
the system to malfunction.
This operation is used to configure the remote control in such a
way that it is compatible with the boiler and the relative system
to which it is connected.
How to configure the operating parameters
1. Set the remote control to the OFF mode.
2. Press and hold down the
and
keys until PAr ap-
pears on the display.
3. To confirm access, press the
key. The display shows the
parameter number instead of the time and the value asso-
ciated with the parameter instead of the temperature. The
parameter number flashes (Figure 4.1
p. 7).
Figure 4.1
Selection of the parameter to be modified
4. Turn the
knob to select the parameter number to be
displayed. The display shows the value associated with the
parameter.
5. To change the value press the
knob: the value associ-
ated with the parameter starts flashing (Figure 4.2
p. 7).
6. Turn the
knob to change the displayed value.
If no key is pressed for a period of 30 seconds, the change
made is aborted and normal operation is restored.
7. Press the
key to save the value.
8. To exit the configuration mode, press
.
Figure 4.2
Changing the selected value (flashing)
The editable parameters are as follows:
▶
P00 Room temperature probe correction
Value to add/subtract (-5.0 °C ÷ +5.0 °C) to the displayed
room temperature to compensate for any errors.
▶
P01 Trip temperature for the room antifreeze function
Trip temperature for the room antifreeze function (0,1 ÷
10,0 °C).
Setting parameter P01 to 0,0 disables the room anti-
freeze function.
▶
P02 Thermal differential (OFF)
Value to be added to the set room setpoint that deter-
mines the end of the heating request.
Example:
T
setpoint
= 20,0 °C
P02 = 0,5 °C
T
setpoint
+ P02 = 20,0 + 0.5 = 20,5 °C
The heat demand ends when the T
room
is greater than
20,5 °C.
▶
P03 Thermal differential (ON)
Value to be subtracted from the set room setpoint that
determines the start of the heating request.
Example:
T
setpoint
= 20,0 °C
P03 = 0,5 °C
T
setpoint
- P03 = 20,0 - 0,5 = 19,5 °C
The heat demand starts when the T
room
is less than 19,5
°C.
▶
P04 Thermoregulation type
0 = On / Off
1 = Modulating on room temperature probe
2 = Modulating on outdoor temperature probe
3 = Modulating on outdoor and room temperature
probes
4 = Disabled
Table 4.1
Operating parameters
Parameter
Description
Value
Default
P00
Room temperature probe correction
-5 / +5 °C
0 °C
P01
Trip temperature for the room antifreeze function
0,1 / 10 °C
0,0 °C = OFF
5 °C
P02
Thermal differential OFF
0,0 / +1 °C
+ 0,3 °C
P03
Thermal differential ON
-1,0 / 0,1 °C
- 0,3 °C
P04
Thermoregulation type
0 - 4
0