Installation and operation manual – remote control 

7

 

4  

 CONFIGURATION OF THE OPERATING PARAMETERS

This Paragraph is reserved exclusively for the author-

ised Robur Technical Assistance Centre.

Incorrect configuration of the remote control may cause 

the system to malfunction.

This operation is used to configure the remote control in such a 

way that it is compatible with the boiler and the relative system 

to which it is connected.

How to configure the operating parameters

1.  Set the remote control to the OFF mode.
2.  Press and hold down the 

 and 

 keys until PAr ap-

pears on the display.

3.  To confirm access, press the 

 key. The display shows the 

parameter number instead of the time and the value asso-

ciated with the parameter instead of the temperature. The 

parameter number flashes (Figure 4.1 

p. 7).

Figure 4.1  

 Selection of the parameter to be modified

 

4.  Turn the 

 knob to select the parameter number to be 

displayed. The display shows the value associated with the 

parameter.

5.  To change the value press the 

 knob: the value associ-

ated with the parameter starts flashing (Figure 4.2 

p. 7).

6.  Turn the 

 knob to change the displayed value.

If no key is pressed for a period of 30 seconds, the change 

made is aborted and normal operation is restored.

7.  Press the 

 key to save the value.

8.  To exit the configuration mode, press 

.

Figure 4.2  

 Changing the selected value (flashing)

The editable parameters are as follows:

 

P00 Room temperature probe correction

Value to add/subtract (-5.0 °C ÷ +5.0 °C) to the displayed 

room temperature to compensate for any errors.

 

P01 Trip temperature for the room antifreeze function

Trip temperature for the room antifreeze function (0,1 ÷ 

10,0 °C).

Setting parameter P01 to 0,0 disables the room anti-

freeze function.

 

P02 Thermal differential (OFF)

Value to be added to the set room setpoint that deter-

mines the end of the heating request.

Example:

T

setpoint

 = 20,0 °C

P02 = 0,5 °C

T

setpoint

 + P02 = 20,0 + 0.5 = 20,5 °C

The heat demand ends when the T

room

 is greater than 

20,5 °C.

 

P03 Thermal differential (ON)

Value to be subtracted from the set room setpoint that 

determines the start of the heating request.

Example:

T

setpoint

 = 20,0 °C

P03 = 0,5 °C

T

setpoint

 - P03 = 20,0 - 0,5 = 19,5 °C

The heat demand starts when the T

room

 is less than 19,5 

°C.

 

P04 Thermoregulation type

0 = On / Off

1 = Modulating on room temperature probe

2 = Modulating on outdoor temperature probe

3 = Modulating on outdoor and room temperature 

probes

4 = Disabled

Table 4.1  

 Operating  parameters

Parameter

Description

Value

Default

P00

Room temperature probe correction

-5 / +5 °C

0 °C

P01

Trip temperature for the room antifreeze function

0,1 / 10 °C

0,0 °C = OFF

5 °C

P02

Thermal differential OFF

0,0 / +1 °C

+ 0,3 °C

P03

Thermal differential ON

-1,0 / 0,1 °C

- 0,3 °C

P04

Thermoregulation type

0 - 4

0

Содержание OCDS006

Страница 1: ...for Caldaria Remote control Installation and operation manual...

Страница 2: ...this publication are not affected With the aim of continuously improving the quality of its products Robur S p A reserves the right to modify the data and contents of this Installation and operation...

Страница 3: ...erature setting p 10 8 5 DHW temperature setting not applicable p 10 8 6 Outdoor probe Kd value setting not applicable p 10 9 Setting manual automatic operation p 10 9 1 Manual operation p 10 9 2 Auto...

Страница 4: ...ing to be made The remote control can be programmed with extreme ease a large LCD display makes this operation easier allowing you to check the settings you have made and to change them at any time Th...

Страница 5: ...lt requiring technical service Night level Day level 3 INSTALLATION For installation of the remote control on the Caldaria Plus refer to the Installation use and maintenance manual supplied with the C...

Страница 6: ...control 5 Fix the remote control to the fixing box by first inserting the upper part and pivoting on it until it is completely closed Figure 3 4 p 6 Figure 3 4 Closing the remote control 6 Power the...

Страница 7: ...save the value 8 To exit the configuration mode press Figure 4 2 Changing the selected value flashing The editable parameters are as follows P00 Room temperature probe correction Value to add subtrac...

Страница 8: ...press the knob within 10 seconds 4 The display shows the flashing number of the parame ter instead of the time and the value associated with the parameter instead of the temperature 5 Turn the knob to...

Страница 9: ...elected state Selected status Identification icon clock day temperature night temperature The value of the item is displayed in the lower left corner instead of the time together with the flashing of...

Страница 10: ...for models of the Caldaria family must be set to 80 C The change of this value will be operative on the boiler until the remote control is con nected to it 8 5 DHW TEMPERATURE SETTING NOT APPLICABLE 8...

Страница 11: ...entification icon of the heating program operation Function Identification icon heating program display PROG not flashing change heating program PROG flashing Once the changes have been made press the...

Страница 12: ...change made Figure 11 1 p 12 3 To deactivate the function before it expires press the key Figure 11 1 Temporary change of the room setpoint 12 FAULT SIGNALS Any faults are displayed by the remote con...

Страница 13: ...o the set tem perature for the active temperature level day night manu al Figure 13 1 p 13 Figure 13 1 Set room temperature display Delivery probe temperature display corresponds to the temperature re...

Страница 14: ...08 00 16 30 22 00 00 00 06 00 08 00 16 30 22 00 Saturday Sunday 00 00 07 00 23 00 00 00 07 00 23 00 How to reset default values 1 Set the remote control to the OFF mode 2 Press and hold down the and k...

Страница 15: ...for antifreeze function 0 0 C OFF 0 1 10 0 C Stop temperature for the room antifreeze function set value 0 6 C Heating time programming resolution 30 minutes Maximum number of daily on off 48 Number...

Страница 16: ...ingonia BG Italy 39 035 888111 F 39 035 884165 www robur it robur robur it Robur is dedicated to dynamic progression in research development and promotion of safe environmentally friendly energy effic...

Отзывы: