Diagnostics
Installation, use and maintenance manual – K18 Simplygas
53
8
Code
Description
Warning (u)
Error (E)
461
Fan fault
Generated as a result of a failed attempt are
restoring warning 439; it is resumed once the
generating cause is resolved. If the code persists,
contact the authorized TAC.
NA
463
Oil pump priming cycle
activated
The priming cycle lasts 30' if activated manually
or 10 minutes if activated automatically.
Reset is automatic when the triggering condi-
tion ceases.
NA
471
DHW buffer tank probe fault
(connected to AUX 3)
Reset is automatic when the triggering condi-
tion ceases.
NA
472
DHW buffer tank probe fault
(connected to AUX 2)
Reset is automatic when the triggering condi-
tion ceases.
NA
473
Manifold probe fault (connec-
ted to AUX 2)
Reset is automatic when the triggering condi-
tion ceases.
NA
474
Manifold probe fault (connec-
ted to AUX 1)
Reset is automatic when the triggering condi-
tion ceases.
NA
478
High hot water delivery
temperature
Check cleanliness of water filters.
Check water flow.
Reset is automatic when the triggering condi-
tion ceases.
NA
480
80
Incomplete functional para-
meters
Invalid configuration para-
meters
Contact the TAC.
481
Invalid bank 1 parameters
Reset is automatic when the triggering condi-
tion ceases.
Contact the TAC.
482
Invalid bank 2 parameters
Reset is automatic when the triggering condi-
tion ceases.
Contact the TAC.
485
Invalid module type configura-
tion parameters
NA
Contact the TAC.
486
ROM board fault
NA
Contact the TAC.
487
pRAM board fault
NA
Contact the TAC.
488
xRAM board fault
NA
Contact the TAC.
489
Registers board fault
NA
Contact the TAC.
490
Outdoor temperature probe
fault
NA
The reset may be done following one of procedures shown in Para-
graph 6.7.3
If the code persists, shows up again or in case of doubt, contact the
TAC.
491
Electronic board fault
NA
Contact the TAC.
492
Weather probe fault (connec-
ted to AUX 1)
Reset is automatic when the triggering condi-
tion ceases.
NA
493
Weather probe fault (connec-
ted to AUX 2)
Reset is automatic when the triggering condi-
tion ceases.
NA
494
Weather probe fault (connec-
ted to AUX 3)
Reset is automatic when the triggering condi-
tion ceases.
NA
495
Auxiliary boiler fault
NA
The restore is automatic and is run after the alarm is reset, which is
to be run
on the auxiliary boiler
(refer to the documentation
of the manufacturer of the auxiliary boiler with regards to the alarm
signalling modes and their resetting operations).
If the reset is successful, i.e. the auxiliary boiler stops signalling the
alarms, but the code persists and reappears, or if in doubt, contact
the Robur TAC; otherwise, contact the TAC of the manufacturer of the
auxiliary boiler for the problem to be resolved.
NA: Not Applicable