![Robur K18 Simplygas Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/robur/k18-simplygas/k18-simplygas_installation-use-and-maintenance-manual_1471522036.webp)
First start-up
36
5
desired water temperature setpoint.
▶
Optionally, if required by the specific auxiliary boiler, by
means of the ON/OFF contact to control switching on and
off and simultaneously the 0-10 V signal for water setpoint
communication only.
If available, you can also connect the alarm signalling output of
the auxiliary boiler to a specific input of the terminal block of the
K18 Simplygas unit.
The output available on the auxiliary boiler must be a volt-
age-free contact and be suitable for SELV type signals (i.e. safety
extra-low voltage), and therefore, it must have double insulation
in comparison to parts powered by the mains.
The auxiliary boiler integration and replacement oper-
ating mode requires the availability and the actual con-
nection of the alarm signalling.
If the alarm signalling is not actually connected and
available, when the control system requests the heat
pump replacement with the auxiliary boiler (under the
integration and replacement operating mode), the con-
trol system will not be able to reactivate the heat pump
as the alarm status of the auxiliary boiler itself will not
be known.
For the description of integration and replacement oper-
ating mode see Paragraph 1.1.5
After consulting the documentation of the heat generator to be
used, connect the ON / OFF contact and/or 0-10 V signal and/or
the alarm indicator, respectively, as shown in Figure 4.14
Figure 4.14
ON/OFF request connection, optional 0-10 V output (tem-
perature setpoint) and optional alarm signal for the auxil-
iary boiler on the unit terminal block
A
K18 Simplygas unit terminal block detail
B
Auxiliary boiler
C
ON/OFF contact request (2x0.75 mm
2
cable)
D
0-10V input for setpoint acquisition (*)
E
Alarm signalling output (mandatory SELV voltage-free contact) (*)
(*) (optional); shielded cable 2x0.75 mm²
ON/OFF
AUX
BOILER
+10
0
+ AL
0 AL
AUX BOILER
A
D
E
C
B
4.10
WINTER KIT (OKBT015)
The use of the optional OKBT015 winter kit protects the conden-
sate drain tray from freezing.
It consists of a heating cable, an antifreeze thermostat, and the
relative electrical wiring.
For installation follow the instructions on the instruction sheet
enclosed with the kit.
Following Figure 4.15
p. 36 shows the winter kit wiring
diagram.
Figure 4.15
Connection of K18 Simplygas winter kit
A
Heat pump module electrical panel
B
Winter kit (OKBT015)
C
2-way Molex connectors
FS Condensate discharge hose heating element
TS Condensate discharge heating element thermostat
1
T
y/g
2-brown
7-blue
N
L
A
B
FS
TS
C
5
FIRST START-UP
First start-up entails checking/setting up the combus-
tion parameters and may exclusively be carried out by a
Robur TAC. NEITHER the user NOR the installation tech-
nician is authorised to perform such operations, under
penalty of voiding the warranty.
The installer is obliged to carry out preliminary checks
described in Paragraph 5.1
5.1
PRELIMINARY CHECKS
Paragraph dedicated to the installer.
5.1.1
Preliminary checks for first start-up
Upon completing installation, before contacting the TAC the in-
staller must check:
▶
Water, electrical and gas systems suitable for the required