Transport and positioning
18
2
outdoor temperature for different water flow rates to the recu-
perator, referring to the ACF 60-00 HR unit.
Consider that in the absence of a refrigeration request no recov-
erable heat output will be available.
Table 1.8
ACF60-00 HR - Heat capacity of the heat recovery unit for
conditions other than nominal ones; flow rate = 2.2 GPM
Heat capacity [Btu/hr] (flow rate = 2.2 GPM)
Hot water return
temperature to
the recovery [°F]
Ambient air temperature [°F]
59
68
77
86
95
104
113
50
92210
92893
93576
93917
95283
96308
97333
68
72743
75134
76978
78549
80188
83330
85379
86
52628
55667
58570
61644
65162
68577
72231
104
35859
39275
42007
46071
50954
55667
61507
122
21857
24248
27356
31761
37567
43714
50818
140
9563
12226
15368
18783
25033
31420
40982
158
—
—
8196
8982
13831
21003
30395
Table 1.9
ACF60-00 HR - Heat capacity of the heat recovery unit for
conditions other than nominal ones; flow rate = 4.4 GPM
Heat capacity [Btu/hr] (flow rate = 4.4 GPM)
Hot water return
temperature to
the recovery [°F]
Ambient air temperature [°F]
59
68
77
86
95
104
113
68
92210
99040
102797 106895 109286
—
—
86
71719
78208
83604
85755
89546
95625
102455
104
47983
54643
61473
65162
71719
78549
85584
122
27765
34083
41426
45149
53004
59868
65640
140
10246
16051
21447
25682
34152
40299
46105
158
—
—
8538
11953
19330
23906
31078
Table 1.10
ACF60-00 HR - Heat capacity of the heat recovery unit for
conditions other than nominal ones; flow rate = 6.6 GPM
Heat capacity [Btu/hr] (flow rate = 6.6 GPM)
Hot water return
temperature to
the recovery [°F]
Ambient air temperature [°F]
59
68
77
86
95
104
113
68
96991
102455 109286
—
—
—
—
86
75134
81964
88795
93269
100406 105871 110993
104
50886
60107
66596
72368
80257
87429
93917
122
30224
38592
44295
50203
56931
64137
71377
140
10929
17076
22779
28346
34152
40982
47813
158
—
—
10587
14344
21174
29029
33469
Table 1.11
ACF60-00 HR - Heat capacity of the heat recovery unit for
conditions other than nominal ones; flow rate = 8.8 GPM
Heat capacity [Btu/hr] (flow rate = 8.8 GPM)
Hot water return
temperature to
the recovery [°F]
Ambient air temperature [°F]
59
68
77
86
95
104
113
68
97333
104709 110993
—
—
—
—
86
76158
83399
91868
97333
—
—
—
104
51228
61302
72094
78549
85106
92210
99040
122
30258
39275
47813
54643
59902
66596
76158
140
14002
17144
24111
29678
35859
42690
49520
158
—
—
12704
17076
22882
29712
35859
Table 1.12
ACF60-00 HR - Heat capacity of the heat recovery unit for
conditions other than nominal ones; flow rate = 11.0 GPM
Heat capacity [Btu/hr] (flow rate = 11.0 GPM)
Hot water return
temperature to
the recovery [°F]
Ambient air temperature [°F]
59
68
77
86
95
104
113
68
103924
—
—
—
—
—
—
86
81281
88795
102455
—
—
—
—
104
57033
64888
76295
82613
88795
97572
102455
122
36884
41255
49520
58058
63454
71104
79061
140
17452
21345
26331
31112
38113
45798
55736
158
—
—
13285
18100
23906
30737
39275
2
TRANSPORT AND POSITIONING
2.1
WARNINGS
Damage from transport or installation
The manufacturer shall not be liable for any damage dur-
ing appliance transport and installation.
On-site inspection
Upon arrival at the site, ensure there is no transport dam-
age on packing, metal panels or finned coil.
After removing the packing materials, ensure the appli-
ance is intact and complete.
Packing
Only remove the packing after placing the appliance on
site.
Do not leave parts of the packing within the reach of
children (plastic, polystyrene, nails...) since they are po-
tentially dangerous.
Weight
The crane and lifting equipment must be suitable for the
load.
Do not stand under suspended loads.
2.2
HANDLING
Handling and lifting
▶
Always handle the appliance in its packing, as delivered by
the factory.
▶
To lift the appliance use straps or slings inserted in the holes
of the base (Figure 2.1
p. 19).
▶
Use lifting beams to avoid damaging the outer panels and
finned coil (Figure 2.1
p. 19).
▶
Comply with safety regulations at the installation site.